US/CA
Menu: Heating parameters > Base line
B
Set the base point of the heating curve
according to the traditional base point/end
point method.
Menu: Heating parameters > Design Temp
B
Set the end point of the heating curve
according to the traditional base point/end
point method.
Menu: Heating parameters > Design supply
temp.
B
Set the supply temperature appropriately for
the heating type of the assigned heating
circuit:
–
For
Radiant Floor
e.g. 114 °F (45 °C)
supply temperature setting.
–
For
Radiators
e.g. 168 °F (75 °C) supply
temperature setting.
–
For
Baseboard
e.g. 176 °F (80 °C) supply
temperature setting.
Menu: Heating parameters > Maximum heating
supply temperature
B
Set the maximum supply temperature
appropriately for the heating type of the
assigned heating circuit:
–
For
Radiant Floor
e.g. 132 °F (55 °C)
maximum supply temperature.
–
For
Radiators
e.g. 176 °F (80 °C)
maximum supply temperature.
–
For
Baseboard
e.g. 176 °F (80 °C)
maximum supply temperature.
Menu: Heating parameters > Room influence
B
Set the room temperature influence on the
heating curve.
–
0%
: No room temperature influence
–
100%
: Maximum room temperature
influence
Menu: Heating parameters > Room influence
enabled for modes
B
Select operating modes for which the room
temperature influence should be active:
–
Eco/Frost
: Room temperature influence is
only active in these operating modes.
–
Comfort/Eco/Frost
: Room temperature
influence is always active.
Factory setting of parameters for
heating curve
Baseline/Design
temp
Radiant Floor
Radiators
Baseboard
Heating surface exponent (fixed
value), curvature of heating curve
–
1.1
1.3
1.4
Minimum outdoor temperature
–
6 °F ( – 15 °C)
6 °F ( – 15 °C) 6 °F ( – 15 °C)
Base line
78 °F (25 °C)
– –
–
Design Temp
168 °F (75 °C)
– –
–
Design supply temp.
–
114 °F (45 °C)
168 °F (75 °C) 176 °F (80 °C)
Maximum heating supply
temperature
176 °F (80 °C)
132 °F (55 °C)
176 °F (80 °C) 176 °F (80 °C)
Room temperature offset
0 °F (0.0 °C)
0 °F (0.0 °C)
0 °F (0.0 °C)
0 °F (0.0 °C)
Heating OFF at outdoor
temperature
68 °F (20 °C)
68 °F (20 °C)
68 °F (20 °C)
68 °F (20 °C)
Tab. 2