DS7060-AUS Reference Guide

6.0  Programming the DS7060

6.1  Address 01 - Zone Programming

 

A zone is an input to the DS7060 Control Communicator.
There are 6 hard-wired zones on the main circuit board.

 

 

Disabled

:  These zones are not monitored, and will not

generate alarm or trouble conditions.

 

Perimeter Instant

:  These zones arm and disarm with

the panel, and never have entry or exit delays. Violation
of this type of zone will cause an intrusion alarm.

 

24-Hour Auxiliary

:  This zone type will cause an

auxiliary alarm.  It is always active. An alarm on a 24-
hour zone (fire or aux.) will be silenced by entering a
disarm code whether the control is armed or not. If the
24-hour zone restores and alarms again the alarm will
sound again. 24-hour zones may generate trouble
conditions during armed or disarmed periods. All 24-
hour zones that have alarmed and are not restored will
show as “Not Ready.” They will prevent arming unless
the panel is force armed. 24-hour zones that have been
bypassed manually will remain so until manually
unbypassed, even if the control is armed and disarmed.
Bypasses of these zones will be displayed on the
keypad.

Perimeter Delayed

:  These zones have entry or exit

delays unless the panel is armed in the “No Entry”
mode. In the “No Entry” mode, the exit delay is in effect
immediately after entering the “No Entry” mode, but is
disabled upon expiration of the exit delay.

 

A delayed zone is ignored during the programmed times
immediately following arming during the exit delay. If
the zone is faulted while the control is armed and not in
exit delay then an entry delay cycle will be started, and
a continuous entry tone will be sounded at the keypads.
If the control is not disarmed by the end of the entry
delay, an alarm will result. There are no keypad tones
during the exit delay unless the feature “Keypad Audible
During Exit Delay” is selected. Refer to Section 6.9,
Address 09. If an entry delay is running and another
entry delay zone is faulted, the entry delay timer is
unaffected and will continue timing from the first entry.
The entry delay time and exit delay time can be set
independently.

 

If a delayed zone remains faulted at the end of an exit
delay, the panel will optionally signal an exit error
condition. The entry delay will be begin as above, and
the alarm output will activate with the pattern selected
for that zone. If the control is not disarmed by the end of
the entry delay, an alarm will result, and an exit error
report will be sent to the central station (following the
alarm report if programmed). The alarm output will
deactivate. If the control is disarmed during the delay
period started by the exit error condition, no reports will
be sent to the central station and any outputs on during
the exit error will deactivate. The exit error report does
not follow the dialer delay option.

 

Interior Follower

:  This zone is not active when the

panel is disarmed, or is armed in the perimeter only
mode. When the zone is active, if a delayed zone is
violated first, this zone is also delayed. If an instant
zone or this zone type is violated first, this zone is not
delayed. This zone is not active during the exit delay.

 

Interior Home/Away

:  This zone becomes interior

instant if the system is armed and an entry/exit delay
zone is violated during the exit delay time. If the system
is armed and an entry/exit zone is not violated, these
zones will be bypassed. These zones are bypassed if
armed perimeter only.

 

Interior Instant

:  These zones arm and disarm with the

panel. They are not active if the panel is armed in the
“perimeter only” mode. They never have entry or exit
delays. Violation of this type of zone will cause an
intrusion alarm.

 

Perimeter Homeguard

:  This zone type is active when

the panel is armed. When the panel is armed perimeter
only, this is a delayed zone. When armed full, this is an
instant zone.

 

Perimeter Follower Homeguard

:  These zones are

always delayed when the panel is armed in the
perimeter only mode. When the panel is fully armed,
these zones are delayed if a delayed zone is violated

Summary of Contents for DS7060

Page 1: ...nly Perimeter Arming with entry delay PIN Perimeter Only Maximum Security Arming PIN No Entry On Force Arming PIN Arming Sequence Bypass Zone Bypass PIN Bypass followed by the Zone number Custom Arm PIN 4 Quick Arm On Turning Off disarming your System PIN Off Commands for other System Features Chime Mode PIN 7 Zone Test PIN 8 1 Read Alarm History PIN 8 9 Battery Test PIN System Reset Communicator ...

Page 2: ...V 800 mA Current draw should be subtracted from either maximum auxiliary or maximum alarm current draw Refer to Section 6 8 for detailed Output operation 2 5 Zones 6 zones 9 if Zone Doubling is used Zone Response Time All six zones can be programmed to respond at either 300 100 ms or a programmable time common to all zones that can be configured to be between 10 ms and 2 5 seconds Zones are ignore...

Page 3: ...he enclosure Knock out the desired wire entrances on the enclosure 3 2 Install the Control Communicator CAUTION The control is static sensitive Make sure you touch earth ground before handling the control This will discharge any static electricity in your body EXAMPLE Run the ground wire to the enclosure before handling the control Then holding the ground wire or using a ground strap install the c...

Page 4: ...e servicing this equipment remove all power including the transformer and battery Also remove the phone line connection A complete functional test is required after any programming CAUTION Incorrect connections may result in damage to the unit NOTE Shared cable is not allowed for keypad telephone or siren wiring ...

Page 5: ... No Entry Only System Reset 3 2 1 6 5 4 9 8 7 0 On No Entry System Reset Bypass Perimeter Only Off Fire Armed Status Power 1 2 3 4 5 6 Armed Status Power Fire On Perimeter Supervisory Bell Silenced Trouble 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 0 No Entry Reset Off Bypass System Only Perimeter DS7447 KEYPAD DS7443 KEYPAD DS7445 KEYPAD This chart will help you understand what each Light LED represents L...

Page 6: ...f an entry delay is running and another entry delay zone is faulted the entry delay timer is unaffected and will continue timing from the first entry The entry delay time and exit delay time can be set independently If a delayed zone remains faulted at the end of an exit delay the panel will optionally signal an exit error condition The entry delay will be begin as above and the alarm output will ...

Page 7: ... fire zone with verification after the two minutes it will start the process over After any fire zone is in alarm all subsequent fire zones are treated as instant no verification until the next fire reset This same procedure will be performed when a SYSTEM RESET is entered except that the two minute instant alarm monitoring period is not observed Since alarm and trouble reporting to the central st...

Page 8: ...ming unless the problem is cleared Forced Armed or Bypassed Trouble on Open Works like Trouble on Short but alarms when loop is opened 6 4 Address 04 Output Type Invisible This is a zone programmed not to have an alarm output or an alarm display at any keypad when activated An alarm signal will be sent but the keypad display will not indicate an alarm while this zone is violated Invisible alarm zo...

Page 9: ...m multiple times per armed period Restore when Disarmed or Reset If the zone returns to normal before the bell timer elapses the alarm display will continue and no restoral will be reported When the bell timer then elapses whether or not the zone has restored the bell will shut down if selected but the alarm display will continue and no restoral will be reported When the system is disarmed or rese...

Page 10: ...d for UL Listed systems Not for use with phone line monitors Ready to Arm System Status This is an output programmed to follow the Status light of the keypad It will activate when the system is ready to arm with no zones violated Follow Burg Alarm This is an output programmed to activate when a zone is in an alarm condition It will remain activated until the system is disarmed or the bell cutoff t...

Page 11: ...ch toggle zone arms the system A double beep will occur 200 ms ON OFF ON when a keyswitch toggle zone disarms the system 6 10 Address 10 General Control Siren on Comm Fail for Silent Zone If programmed a silent zone will sound the alarm outputs if the zone is in an alarm condition and the system fails to communicate with the central station Closing Ringback If programmed the keypad sounders and Ou...

Page 12: ...The keypad type LED or Alpha or no keypad must be programmed 6 12 Address 12 thru 18 Alpha Label Address 12 Private Label The private label will display when the system is Ready to Arm and when it is Armed Address 13 Zone 1 Alpha Label Address 14 Zone 2 Alpha Label Address 15 Zone 3 Alpha Label Address 16 Zone 4 Alpha Label Address 17 Zone 5 Alpha Label Address 18 Zone 6 Alpha Label Armed Status P...

Page 13: ...pad entry area is the Fire Key If programmed the key will activate a fire alarm when pressed for 2 seconds May not be programmed as an invisible alarm Help Key B The help key at the bottom center of the keypad entry area is the Help Key If programmed the key will activate a supplementary or an auxiliary type alarm when pressed for 2 seconds Panic Key C The emergency key at the bottom right of the ...

Page 14: ...loading When enabled if an attempt is made to connect to the panel for a remote programming session the panel will hang up and callback the number programmed for Phone 3 Address 44 and 45 Ring Count The control panel can be programmed to answer the phone after a selected number of rings for remote programming access WDSRP Baud Rate This selection determines the baud rate that the panel will use to...

Page 15: ...ats Contact ID SIA 4 9 have well defined reports that are sent regardless of the value programmed in the report code location Any non zero value programmed in the report code location will send the appropriate report Special Formats Personal Dialing Format Pager are not recommended for primary reporting If they are used Personal Dialing Format could use the same report codes as the Pulsed Formats ...

Page 16: ...Trouble Restoral This report is sent when the zone trouble condition is cleared 6 23 Address 29 Zone Bypass Report Zone Bypass Reports are sent with the Closing Report Address 20 digit 1 left most digit must be set for 2 or 3 for these reports 6 24 Address 30 Zone Bypass Restoral Report Zone Bypass Restoral Reports are only sent with an Opening Report Address 20 digit 1 left most digit must be set...

Page 17: ...is sent when the system is disarmed after an alarm has occurred It will also be sent if the system is already disarmed and a user number is entered to silence a 24 hour or fire zone 6 26 Address 32 Battery AC Report Low Battery Report This report is sent when a low battery condition occurs Low Battery Restoral Report This report is sent when a low battery condition restores AC Failure Report This ...

Page 18: ... This report is sent after there has been a communicator failure Retries will occur after 30 minutes then every 24 hours or when a new event occurs When the next successful communicator attempt occurs this report will be included 6 30 Address 36 Test Reports System Test Automatic Test Report This report is sent at fixed intervals determined by programming Address 48 Automatic Test Report Interval ...

Page 19: ... Address 44 45 Phone 3 Remote Programming Address 40 Phone 1 digits 1 16 Address 41 Phone 1 digits 17 32 Address 42 Phone 2 digits 1 16 Address 43 Phone 2 digits 17 32 Address 44 Phone 3 digits 1 16 Address 45 Phone 3 digits 17 32 Note To dial the character enter 1 the character is sent as 1 1 when pulse dialing The letter B will be displayed To dial the character enter 2 the character is only val...

Page 20: ...t Set this value to the number of hours from the time the panel was powered up for the first report Example If the panel was powered up at 2 PM and you want test reports at 3 AM set to 0 1 3 2 PM 13 hours 3 AM If not set the first report will be sent 12 hours after panel power up 6 38 Address 50 AC Failure Report Delay Address 32 must be programmed to this report NOTE If AC power should restore be...

Page 21: ...g adds three additional specific zones to the control panel Zone 7 Fire Supervised for use with 4 wire smoke detectors Zone 8 Tamper Supervised for use with tamper switches Zone 9 Keyswitch Supervised keyswitch input A momentary contact closure on this input will toggle the panel between the armed and disarmed states NOTE The zone input wiring and End Of Line resistors differ if Zone Doubling is s...

Page 22: ... Reference Guide 6 44 Address 58 Custom Chime Custom Chime determines which zones will chime in the chime mode Only Zones programmed as Perimeter Instant Perimeter Delayed Perimeter Homeguard or Perimeter Homeguard Follower in Address 01 can be chime zones ...

Page 23: ...ME Example 1038 Thomas J Brown User 01 User 02 User 03 User 04 User 05 User 06 User 07 User 08 User 09 User 10 User 11 User 12 User 13 User 14 User 15 DEVICE LOCATION TYPE Example PIR Kitchen Invisible alarm alarm on short alarm on open 24 hour Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 ...

Page 24: ...tion Systems Inc 130 Perinton Parkway Fairport New York USA 14450 9199 585 223 4060 888 289 0096 Fax 585 223 9810 Copyright 2001 Detection Systems Inc DS7060 AUS Reference Guide P N 36624E 9 01 Page 24 of 24 ...

Reviews: