DS7060-AUS Reference Guide

Copyright 

 2001 Detection Systems, Inc.

Page 7

first, or instant if this zone or an instant zone is violated
first.

 

Silence Audible

:  A zone configured as Silence Audible

will, when activated, cause the panel to shut off output
PO3 and keypad sounders.  When this zone restores,
the sounders will reactivate (if the timeout has not
expired). It is used to facilitate voice communication for
listen-in modules.

 

Keyswitch Toggle:

  Each time this zone is closed, it

will toggle the armed state of the panel.  It has a 300
ms response time. No alarms or trouble conditions are
generated by a zone of this type. Optionally, to support
this feature, the panel will generate a single siren beep
for arm actions and a double beep for disarm actions.

 

NOTE 1:

 If “Auto Bypass” is enabled (Address 10),

Keyswitch Toggle will force arm a “Not Ready” zone.

 

NOTE 2:

 Zone 9 is pre-programmed as a Keyswitch

Toggle zone.

 

Keyswitch On/Off:

  Not available when zone doubling

is used. When this zone is closed, it will arm the panel.
When it is shunted by an EOL (supervised), the panel
will be disarmed. No alarms or trouble conditions will be
generated by a zone of this type. Opening the zone will
not affect the arming state of the control. When this
option is selected, keypads can not be used to arm or
disarm the system unless the keyswitch zone is
manually bypassed, prior to arming the system, from
the keypad. If the keyswitch zone is bypassed, any
keypad can perform all arming and disarming functions.

 

NOTE:

 If “Auto Bypass” is enabled (Address 10),

Keyswitch On/Off will force arm a “Not Ready” zone.

 

24-Hour Fire with Verification:

  If a fire zone alarms

and it is programmed for verification, the control will
interrupt the programmable output(s) set as a switched
power return for 10 seconds. During the 10 second
power interruption, and for 15 seconds after power
restoral, it will ignore all zone status on all fire zones (to
ignore inrush currents). After fifteen seconds, it will
monitor all fire zones for two minutes. If any fire zone
returns to alarm within the two minute window it will
create a fire alarm condition. If a fire zone does not go
into alarm within the two minute window it will disregard
the initial trip. If another alarm occurs on a fire zone
with verification after the two minutes, it will start the
process over. After any fire zone is in alarm, all
subsequent fire zones are treated as instant (no
verification) until the next fire reset. This same
procedure will be performed when a [SYSTEM RESET]
is entered, except that the two minute instant alarm
monitoring period is not observed.

 

Since alarm and trouble reporting to the central station
for fire zones is the same as for burg zones (i.e. it is
based on the state of the zone) it is possible for Fire,
and Fire Trouble restoral signals to be transmitted even
though the panel may still be displaying these zone
conditions. This is because the displays are latched until
cleared by an operator action.

 

NOTE:

The use of the controls fire alarm verification
feature may not be permitted in some areas.
Check your local fire/building codes.

 

Fire:

  This zone is active and will alarm all 24 hours of

the day regardless of the arming state of the control. An
alarm on a fire zone will be silenced by entering a
disarm code whether the control is armed or not. If the
fire zone restores and alarms again the alarm will
sound again. An open during the armed or disarmed
period will send a trouble report and not an alarm. Fire
zones are never silent, invisible, or swinger shunted. All
fire zones that have alarmed will continue to show on all
keypads until a fire reset is performed, even if they have
physically restored. Fire zones may not be bypassed
using the BYPASS command.

 

NOTE:

If force arming is enabled (see programming
address 10), force arming is possible when the
fire zone is violated (shorted).

 

Interior Delayed:

 This is a zone programmed to be

ignored during the entry delay period. If it is violated
when the system is armed, it will activate a delay for the
programmed entry delay time. The keypad pre-alert
sounders will activate and the alarm system may be
disarmed during this delay period. If the system is not
disarmed during this delay period, this zone will activate
an alarm.

 

 

Day Monitor:

 This is a zone programmed to be a

perimeter instant zone when the system is armed.
When the system is disarmed, any violation of this zone
will activate the keypad sounders which will sound
continuously until a disarm sequence is entered. The
alarm outputs for this zone will not activate and there
will be no report sent for this zone when the system is
disarmed. This zone will report a trouble condition if
programmed.

Summary of Contents for DS7060

Page 1: ...nly Perimeter Arming with entry delay PIN Perimeter Only Maximum Security Arming PIN No Entry On Force Arming PIN Arming Sequence Bypass Zone Bypass PIN Bypass followed by the Zone number Custom Arm PIN 4 Quick Arm On Turning Off disarming your System PIN Off Commands for other System Features Chime Mode PIN 7 Zone Test PIN 8 1 Read Alarm History PIN 8 9 Battery Test PIN System Reset Communicator ...

Page 2: ...V 800 mA Current draw should be subtracted from either maximum auxiliary or maximum alarm current draw Refer to Section 6 8 for detailed Output operation 2 5 Zones 6 zones 9 if Zone Doubling is used Zone Response Time All six zones can be programmed to respond at either 300 100 ms or a programmable time common to all zones that can be configured to be between 10 ms and 2 5 seconds Zones are ignore...

Page 3: ...he enclosure Knock out the desired wire entrances on the enclosure 3 2 Install the Control Communicator CAUTION The control is static sensitive Make sure you touch earth ground before handling the control This will discharge any static electricity in your body EXAMPLE Run the ground wire to the enclosure before handling the control Then holding the ground wire or using a ground strap install the c...

Page 4: ...e servicing this equipment remove all power including the transformer and battery Also remove the phone line connection A complete functional test is required after any programming CAUTION Incorrect connections may result in damage to the unit NOTE Shared cable is not allowed for keypad telephone or siren wiring ...

Page 5: ... No Entry Only System Reset 3 2 1 6 5 4 9 8 7 0 On No Entry System Reset Bypass Perimeter Only Off Fire Armed Status Power 1 2 3 4 5 6 Armed Status Power Fire On Perimeter Supervisory Bell Silenced Trouble 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 0 No Entry Reset Off Bypass System Only Perimeter DS7447 KEYPAD DS7443 KEYPAD DS7445 KEYPAD This chart will help you understand what each Light LED represents L...

Page 6: ...f an entry delay is running and another entry delay zone is faulted the entry delay timer is unaffected and will continue timing from the first entry The entry delay time and exit delay time can be set independently If a delayed zone remains faulted at the end of an exit delay the panel will optionally signal an exit error condition The entry delay will be begin as above and the alarm output will ...

Page 7: ... fire zone with verification after the two minutes it will start the process over After any fire zone is in alarm all subsequent fire zones are treated as instant no verification until the next fire reset This same procedure will be performed when a SYSTEM RESET is entered except that the two minute instant alarm monitoring period is not observed Since alarm and trouble reporting to the central st...

Page 8: ...ming unless the problem is cleared Forced Armed or Bypassed Trouble on Open Works like Trouble on Short but alarms when loop is opened 6 4 Address 04 Output Type Invisible This is a zone programmed not to have an alarm output or an alarm display at any keypad when activated An alarm signal will be sent but the keypad display will not indicate an alarm while this zone is violated Invisible alarm zo...

Page 9: ...m multiple times per armed period Restore when Disarmed or Reset If the zone returns to normal before the bell timer elapses the alarm display will continue and no restoral will be reported When the bell timer then elapses whether or not the zone has restored the bell will shut down if selected but the alarm display will continue and no restoral will be reported When the system is disarmed or rese...

Page 10: ...d for UL Listed systems Not for use with phone line monitors Ready to Arm System Status This is an output programmed to follow the Status light of the keypad It will activate when the system is ready to arm with no zones violated Follow Burg Alarm This is an output programmed to activate when a zone is in an alarm condition It will remain activated until the system is disarmed or the bell cutoff t...

Page 11: ...ch toggle zone arms the system A double beep will occur 200 ms ON OFF ON when a keyswitch toggle zone disarms the system 6 10 Address 10 General Control Siren on Comm Fail for Silent Zone If programmed a silent zone will sound the alarm outputs if the zone is in an alarm condition and the system fails to communicate with the central station Closing Ringback If programmed the keypad sounders and Ou...

Page 12: ...The keypad type LED or Alpha or no keypad must be programmed 6 12 Address 12 thru 18 Alpha Label Address 12 Private Label The private label will display when the system is Ready to Arm and when it is Armed Address 13 Zone 1 Alpha Label Address 14 Zone 2 Alpha Label Address 15 Zone 3 Alpha Label Address 16 Zone 4 Alpha Label Address 17 Zone 5 Alpha Label Address 18 Zone 6 Alpha Label Armed Status P...

Page 13: ...pad entry area is the Fire Key If programmed the key will activate a fire alarm when pressed for 2 seconds May not be programmed as an invisible alarm Help Key B The help key at the bottom center of the keypad entry area is the Help Key If programmed the key will activate a supplementary or an auxiliary type alarm when pressed for 2 seconds Panic Key C The emergency key at the bottom right of the ...

Page 14: ...loading When enabled if an attempt is made to connect to the panel for a remote programming session the panel will hang up and callback the number programmed for Phone 3 Address 44 and 45 Ring Count The control panel can be programmed to answer the phone after a selected number of rings for remote programming access WDSRP Baud Rate This selection determines the baud rate that the panel will use to...

Page 15: ...ats Contact ID SIA 4 9 have well defined reports that are sent regardless of the value programmed in the report code location Any non zero value programmed in the report code location will send the appropriate report Special Formats Personal Dialing Format Pager are not recommended for primary reporting If they are used Personal Dialing Format could use the same report codes as the Pulsed Formats ...

Page 16: ...Trouble Restoral This report is sent when the zone trouble condition is cleared 6 23 Address 29 Zone Bypass Report Zone Bypass Reports are sent with the Closing Report Address 20 digit 1 left most digit must be set for 2 or 3 for these reports 6 24 Address 30 Zone Bypass Restoral Report Zone Bypass Restoral Reports are only sent with an Opening Report Address 20 digit 1 left most digit must be set...

Page 17: ...is sent when the system is disarmed after an alarm has occurred It will also be sent if the system is already disarmed and a user number is entered to silence a 24 hour or fire zone 6 26 Address 32 Battery AC Report Low Battery Report This report is sent when a low battery condition occurs Low Battery Restoral Report This report is sent when a low battery condition restores AC Failure Report This ...

Page 18: ... This report is sent after there has been a communicator failure Retries will occur after 30 minutes then every 24 hours or when a new event occurs When the next successful communicator attempt occurs this report will be included 6 30 Address 36 Test Reports System Test Automatic Test Report This report is sent at fixed intervals determined by programming Address 48 Automatic Test Report Interval ...

Page 19: ... Address 44 45 Phone 3 Remote Programming Address 40 Phone 1 digits 1 16 Address 41 Phone 1 digits 17 32 Address 42 Phone 2 digits 1 16 Address 43 Phone 2 digits 17 32 Address 44 Phone 3 digits 1 16 Address 45 Phone 3 digits 17 32 Note To dial the character enter 1 the character is sent as 1 1 when pulse dialing The letter B will be displayed To dial the character enter 2 the character is only val...

Page 20: ...t Set this value to the number of hours from the time the panel was powered up for the first report Example If the panel was powered up at 2 PM and you want test reports at 3 AM set to 0 1 3 2 PM 13 hours 3 AM If not set the first report will be sent 12 hours after panel power up 6 38 Address 50 AC Failure Report Delay Address 32 must be programmed to this report NOTE If AC power should restore be...

Page 21: ...g adds three additional specific zones to the control panel Zone 7 Fire Supervised for use with 4 wire smoke detectors Zone 8 Tamper Supervised for use with tamper switches Zone 9 Keyswitch Supervised keyswitch input A momentary contact closure on this input will toggle the panel between the armed and disarmed states NOTE The zone input wiring and End Of Line resistors differ if Zone Doubling is s...

Page 22: ... Reference Guide 6 44 Address 58 Custom Chime Custom Chime determines which zones will chime in the chime mode Only Zones programmed as Perimeter Instant Perimeter Delayed Perimeter Homeguard or Perimeter Homeguard Follower in Address 01 can be chime zones ...

Page 23: ...ME Example 1038 Thomas J Brown User 01 User 02 User 03 User 04 User 05 User 06 User 07 User 08 User 09 User 10 User 11 User 12 User 13 User 14 User 15 DEVICE LOCATION TYPE Example PIR Kitchen Invisible alarm alarm on short alarm on open 24 hour Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 Zone 1 ...

Page 24: ...tion Systems Inc 130 Perinton Parkway Fairport New York USA 14450 9199 585 223 4060 888 289 0096 Fax 585 223 9810 Copyright 2001 Detection Systems Inc DS7060 AUS Reference Guide P N 36624E 9 01 Page 24 of 24 ...

Reviews: