DS7060-AUS Reference Guide
Copyright
2001 Detection Systems, Inc.
Page 11
6.9 Address 09 - User Control
•
Duress Code:
If this option is selected and Code 14 is
used to disarm the system, a duress report will be sent
as the system is otherwise disarmed normally. User
Code 14 will not arm the system, or report duress, if the
system is not armed.
•
Guest Code:
If this option is selected, Code 15 is a
guest code. It can be enabled by pressing [PIN] [#] [8]
[4]. It will remain active until the panel is disarmed with
any other valid code.
•
Arming Warning:
If this option is selected, the alarm
output will turn on for 2 seconds when the panel is
armed.
•
Keypad Audible During Exit Delay:
Selection of this
option will cause the keypad sounders to beep during
the exit delay time. A one second beep will sound at 5
second intervals, changing to a 3-beep tone at 10 and 5
seconds prior to the end of the delay.
•
Keyswitch Arming Warning:
Selecting this option will
activate any output programmed as Intrusion, Follow
Burg Alarm, or Follow Burg Alarm and Fire Alarm. The
output will beep once (200 ms ON) when a keyswitch
toggle zone arms the system. A double beep will occur
(200 ms ON-OFF-ON) when a keyswitch toggle zone
disarms the system.
6.10 Address 10 - General Control
•
Siren on Comm. Fail for Silent Zone:
If programmed,
a silent zone will sound the alarm outputs if the zone is
in an alarm condition and the system fails to
communicate with the central station.
•
Closing Ringback:
If programmed, the keypad
sounders and Output 3 will activate for 2 seconds after
the system is armed and the closing report is
successfully sent. This requires Closing Ringback and
Closing Report to be programmed. If the panel does not
report to a central station, use “Arming Warning” in
Address 9.
•
Swinger Shunt:
If enabled, a zone can only alarm or
trouble up to three times per armed period. After the
third alarm or trouble, the zone will be bypassed and a
bypass report for this zone will be sent. Fire zones are
never swinger shunted.
•
50 Hz/60 Hz:
Set to local power type. The panel clock
is synchronized to the power line frequency. 60 Hz
required for UL Listed Requirements.
•
Keypad Mode:
Commercial Mode requires a PIN
number for all functions. Residential Mode only requires
a PIN number for disarming and silencing alarms.
•
Quick Arm:
If enabled, a PIN is not needed to arm.
NOTE
: Used only in conjunction with commercial
mode.