DS7060-AUS Reference Guide
1.0 System Overview
The DS7060 Control/Communicator is a fully integrated
hard-wire security and residential fire alarm system. It can
support up to 6 input zones and 15 individual users. Up to
4 keypads may be used to provide user interface with the
system, as well as programming access for the installer.
2.0 Specifications
2.1 Enclosure Housing
The enclosure is manufactured from 22 Ga. (0.65 mm),
cold-rolled steel, and measures 9.25" Wide, by 10.25"
High, by 3" Deep (23.5 cm Wide, by 26 cm High, by 7.6
cm Deep). The door has a knockout for a standard DS
lock (optional). The enclosure has a slot in the back and
also has an optional tamper switch mounting bracket with
a plunger switch.
2.2 Temperature
•
Operating temp:
+32° to +120°F (0° to +49°C)
•
Storage temp:
-20° to +150°F (-28° to +66°C)
2.3 Power
•
Input Power: 16.5 VAC (U.S.) 16 VAC (Aust), 20 VA,
50 or 60 Hz
•
Auxiliary Regulated Power:
12-12.5 VDC, 0.8 A
•
Auxiliary Power Voltage Range: 10 to 13.8 VDC
•
Optional Standby battery (P334):
12 V, 7.0 AH
•
Control Panel Current Draw:
65 mA
•
DS7443 Keypad Current Draw: 45 mA, Standby
45 mA, Alarm
•
DS7445 Keypad Current Draw: 75 mA, Standby
75 mA, Alarm
•
DS7447 Keypad Current Draw: 100 mA, Standby
100mA, Alarm
•
Fuse 1 and 2:
1 A, 250 V
2.4 Outputs
•
Programmable Output 1*: Solid state, switch to
ground (500 mA max.).
•
Programmable Output 2*: Solid state, switch to
ground (500 mA max.).
•
Programmable Output 3*: Form “C” relay contacts
available. Typical: Normally Open contacts that switch
to 12 V @ 800 mA.
* = Current draw should be subtracted from either
maximum auxiliary or maximum alarm current draw.
Refer to Section 6.8 for detailed Output operation.
2.5 Zones
•
6 zones (9 if Zone Doubling is used)
•
Zone Response Time: All six zones can be
programmed to respond at either 300 ±100 ms or a
programmable time (common to all zones) that can be
configured to be between 10 ms and 2.5 seconds.
Zones are ignored for 15 seconds after power up, and
for two seconds after a system reset.
Refer to Sections 6.2 - 6.7 for detailed zone operation.
2.6 Keypads
•
Total number of keypads:
4 Keypads
•
Max. wire length total in system: 1000 ft. (305 m)
•
Wire type:
22 AWG (0.8 mm)
NOTE:
Keypads may be up to 1000 ft. (305 m) from the
panel when #22 (0.8 mm) wire is used and only
one keypad is connected to a particular wire run.
2.7 Communicator
Will report to two phone numbers with full single, double,
and backup reporting. Communicated in 3/1, 3/1E, 3/1
with Parity, 3/1E with Parity, 4/1, 4/2, High Speed 4/9,
Pager, Contact ID, and Personal Dialing formats.
Refer to Sections 6.14 - 6.33 for communicator operation.
The ringer equivalence is 0.1 B.
2.8 Users
The system allows up to 15 individual users. Each user
will have his own PIN number (the 4 digit code entered at
the keypads).
2.9 Lightning Protection
MOVs and/or spark gaps provide protection from lightning
surges and static discharges.
2.10 Burglar/Fire Zone Inputs
•
Number of Circuits:
6 Circuits on board
•
End-of-Line Resistor:
2.21k ohms
NOTE:
4 wire type smoke detectors only.
2.11 Line Seizure Notice
This control panel incorporates a line seizure feature which
will disable internal telephone lines when the control panel
is sending alarm or supervision reports to the central
station.