background image

High-Voltage Conventional Duct Detector

 Mounting | en

5

Bosch Security Systems, Inc.

Installation Guide

F.01U.

035.635

 | 5.0 | 2011.09

3.2

Verifying Air Flow and Direction

Use the D300A-HV in ducts with air velocities between 300 ft to 4000 ft (91 m to 1219 m) per 

minute. Verify the air velocity by checking the duct installation specifications, or by using an 

Alnor Model 6000P (or equivalent) velocity meter. Refer to 

Figure 3.2

 on page 5 for sampling 

tube orientation to air flow direction. 

Figure 3.1

Mount the Duct Housing

Figure 3.2

Intake Sampling Tube Orientation

1 -

Six duct widths (minimum) from any 

bend or other obstruction

7 -

Exhaust tube

2 -

Air duct 

8 -

Set screws (2)

3 -

Template

9 -

Intake sampling tube connectors (2)

4 -

Stopper

10 - Duct mounting screws (2)

5 -

Air flow for this illustration

11 - Top of the D300A-HV Housing

6 -

Intake sampling tube

1 -

Insert stopper at this end of the 

intake sampling tube.

5 -

Exhaust tube (2)

2 -

Air flow

6 -

Air holes (6)

3 -

Intake sampling tube (2)

7 -

Set screws (4)

4 -

Duct width*

8 -

Tops of the D300A-HV Housings

* Support the intake sampling tube where the duct width is greater than 3 ft (91 cm).

1

Summary of Contents for D300A-HV

Page 1: ...High Voltage Conventional Duct Detector D300A HV en Installation Guide ...

Page 2: ......

Page 3: ...ble of Contents 1 Notice 4 2 Overview 4 3 Mounting 4 3 1 Preparing the Duct 4 3 2 Verifying Air Flow and Direction 5 3 3 Assembling the Intake Sampling Tubes 6 3 4 Mounting the Intake Sampling Tubes 6 3 5 Mounting the Detector 6 3 6 Verifying the Air Sampling 6 4 Wiring 6 4 1 Testing 8 4 2 Replacing the Detector Head 8 5 Specifications 8 ...

Page 4: ... 3 Mounting 3 1 Preparing the Duct When preparing the duct refer to Figure 3 1 on page 5 1 Remove the paper backing from the mounting template included in the Installation Kit 2 Attach the template to the duct at the desired location 3 Using the template as a guide drill four mounting holes 3 32 in 2 38 mm diameter for the duct mounting screws four 12 x in 1 27 cm sheet metal screws packaged in in...

Page 5: ...ientation to air flow direction Figure 3 1 Mount the Duct Housing Figure 3 2 Intake Sampling Tube Orientation 1 Six duct widths minimum from any bend or other obstruction 7 Exhaust tube 2 Air duct 8 Set screws 2 3 Template 9 Intake sampling tube connectors 2 4 Stopper 10 Duct mounting screws 2 5 Air flow for this illustration 11 Top of the D300A HV Housing 6 Intake sampling tube 1 Insert stopper a...

Page 6: ... tubes and tighten Refer to Figure 3 1 on page 5 for mounting details 3 5 Mounting the Detector 1 Position the detector and intake sampling tube assembly in the desired location 2 Using four duct mounting screws four 12 x in 1 27 cm sheet metal screws included in the installation kit attach the D300A HV on the duct 3 6 Verifying the Air Sampling Use a Dwyer Model 4000 Differential Pressure Gauge o...

Page 7: ...Wiring the D300A to an FACP 1 Switche Power connections upon reset connect items 2 or 3 not both 5 Alarm contacts 1 A at 24 VDC 2 230 VAC 60 Hz input at 0 1 A maximum 6 Trouble contacts 10 A at 115 VAC 3 24 VAC VDC 60 Hz input at 0 1 A maximum detector only Up to 1 9 A for auxiliary outputs 7 Remote accessories 4 Alarm contacts 10 A at 115 VAC Trouble contacts are shown in non energized condition ...

Page 8: ...ectric Smoke Detector Head 1 Remove the four screws holding the detector s cover 2 Remove the existing detector head by twisting it counterclockwise 3 Insert the D282A DH and turn it clockwise 4 Replace the detector s cover and tighten the screws 5 Specifications 1 1 2 kΩ 1 W current limiting resistor 3 Key or push button Test Reset switch 4 A at 24 VDC 2 Red ALARM LED 15 mA at 24 VDC 4 Green Pilo...

Page 9: ...urity Systems Inc Installation Guide F 01U 035 635 5 0 2011 09 Humidity 10 RH to 85 RH non condensing Intake Sampling Tubes FAA 325 2 5 2 5 ft 0 8m FAA 325 5 5 0 ft 1 5m FAA 325 10 10 ft 3m Replacement Detector Head D282A DH Replacement Photoelectric Smoke Detector Head ...

Page 10: ...10 en Specifications High Voltage Conventional Duct Detector F 01U 035 635 5 0 2011 09 Installation Guide Bosch Security Systems Inc ...

Page 11: ......

Page 12: ...Bosch Security Systems Inc 130 Perinton Parkway NY 14450 Fairport USA www boschsecurity us Bosch Security Systems Inc 2011 ...

Reviews: