The D300A-HV photoelectric detector has a built-in sensitivity window verification feature. If 

the detector is within its calibrated sensitivity range, the detector LEDs flash green in standby 

or normal operation. If the detector drifts outside its sensitivity range, the LEDs flash red to 

indicate an out of sensitivity condition. Bosch D1000 Calibrated Smoke Detector Tester may 

also be used to check sensitivity.

4.2

Replacing the Detector Head

If the detector head supplied with the D300A-HV must be replaced, only replace the existing 

head with a D282A-DH Replacement Photoelectric Smoke Detector Head.

1.

Remove the four screws holding the detector’s cover.

2.

Remove the existing detector head by twisting it counterclockwise.

3.

Insert the D282A-DH and turn it clockwise.

4.

Replace the detector’s cover and tighten the screws.

5

Specifications

1 -

1.2 kΩ, 1 W current-limiting resistor

3 -

Key or push button “Test/Reset” switch 

(4 A at 24 VDC) 

2 -

Red "ALARM LED" (15 mA at 24 VDC)

4 -

Green “Pilot” LED (15 mA at 24 VDC)

Black (-)

Red (+)

1

4

3

Black (-)

Red (+)

1

2

17

16

20

16

18

19

3

Standby Current

20 mA at 24 VAC

13 mA at 24 VDC

8 mA at 230 VAC

Alarm Current

95 mA at 24 VAC

60 mA at 24 VDC

15 mA at 230 VAC

Alarm Relay Contact Rating

10 A maximum at 250 VAC resistive

Trouble Relay Contact Rating

10 A maximum at 250 VAC resistive

Sensitivity Range (Factory Set)

1.5%/ft to ~2.75%/ft (4.8%/m to ~ 8.7%/m)

Differential

 

Pressure

0.01 in. (0.25 mm) - 1 in. (3 cm) of water

Air Velocity

300 ft/min to 4000 ft/min (91 m/min to 1219 m/

min) 

Ambient Temperature

+32°F to +120°F (0°C to +49°C )

Summary of Contents for D300A-HV

Page 1: ...High Voltage Conventional Duct Detector D300A HV en Installation Guide ...

Page 2: ......

Page 3: ...ble of Contents 1 Notice 4 2 Overview 4 3 Mounting 4 3 1 Preparing the Duct 4 3 2 Verifying Air Flow and Direction 5 3 3 Assembling the Intake Sampling Tubes 6 3 4 Mounting the Intake Sampling Tubes 6 3 5 Mounting the Detector 6 3 6 Verifying the Air Sampling 6 4 Wiring 6 4 1 Testing 8 4 2 Replacing the Detector Head 8 5 Specifications 8 ...

Page 4: ... 3 Mounting 3 1 Preparing the Duct When preparing the duct refer to Figure 3 1 on page 5 1 Remove the paper backing from the mounting template included in the Installation Kit 2 Attach the template to the duct at the desired location 3 Using the template as a guide drill four mounting holes 3 32 in 2 38 mm diameter for the duct mounting screws four 12 x in 1 27 cm sheet metal screws packaged in in...

Page 5: ...ientation to air flow direction Figure 3 1 Mount the Duct Housing Figure 3 2 Intake Sampling Tube Orientation 1 Six duct widths minimum from any bend or other obstruction 7 Exhaust tube 2 Air duct 8 Set screws 2 3 Template 9 Intake sampling tube connectors 2 4 Stopper 10 Duct mounting screws 2 5 Air flow for this illustration 11 Top of the D300A HV Housing 6 Intake sampling tube 1 Insert stopper a...

Page 6: ... tubes and tighten Refer to Figure 3 1 on page 5 for mounting details 3 5 Mounting the Detector 1 Position the detector and intake sampling tube assembly in the desired location 2 Using four duct mounting screws four 12 x in 1 27 cm sheet metal screws included in the installation kit attach the D300A HV on the duct 3 6 Verifying the Air Sampling Use a Dwyer Model 4000 Differential Pressure Gauge o...

Page 7: ...Wiring the D300A to an FACP 1 Switche Power connections upon reset connect items 2 or 3 not both 5 Alarm contacts 1 A at 24 VDC 2 230 VAC 60 Hz input at 0 1 A maximum 6 Trouble contacts 10 A at 115 VAC 3 24 VAC VDC 60 Hz input at 0 1 A maximum detector only Up to 1 9 A for auxiliary outputs 7 Remote accessories 4 Alarm contacts 10 A at 115 VAC Trouble contacts are shown in non energized condition ...

Page 8: ...ectric Smoke Detector Head 1 Remove the four screws holding the detector s cover 2 Remove the existing detector head by twisting it counterclockwise 3 Insert the D282A DH and turn it clockwise 4 Replace the detector s cover and tighten the screws 5 Specifications 1 1 2 kΩ 1 W current limiting resistor 3 Key or push button Test Reset switch 4 A at 24 VDC 2 Red ALARM LED 15 mA at 24 VDC 4 Green Pilo...

Page 9: ...urity Systems Inc Installation Guide F 01U 035 635 5 0 2011 09 Humidity 10 RH to 85 RH non condensing Intake Sampling Tubes FAA 325 2 5 2 5 ft 0 8m FAA 325 5 5 0 ft 1 5m FAA 325 10 10 ft 3m Replacement Detector Head D282A DH Replacement Photoelectric Smoke Detector Head ...

Page 10: ...10 en Specifications High Voltage Conventional Duct Detector F 01U 035 635 5 0 2011 09 Installation Guide Bosch Security Systems Inc ...

Page 11: ......

Page 12: ...Bosch Security Systems Inc 130 Perinton Parkway NY 14450 Fairport USA www boschsecurity us Bosch Security Systems Inc 2011 ...

Reviews: