nstallation Guide
B
osch Security Systems, Inc.
Figure 4.3
Remote Access Memory
4.1
Testing
The D300A-HV photoelectric detector has a built-in sensitivity window verification feature. If
the detector is within its calibrated sensitivity range, the detector LEDs flash green in standby
or normal operation. If the detector drifts outside its sensitivity range, the LEDs flash red to
indicate an out of sensitivity condition. Bosch D1000 Calibrated Smoke Detector Tester may
also be used to check sensitivity.
4.2
Replacing the Detector Head
If the detector head supplied with the D300A-HV must be replaced, only replace the existing
head with a D282A-DH Replacement Photoelectric Smoke Detector Head.
1.
Remove the four screws holding the detector’s cover.
2.
Remove the existing detector head by twisting it counterclockwise.
3.
Insert the D282A-DH and turn it clockwise.
4.
Replace the detector’s cover and tighten the screws.
5
Specifications
1 -
1.2 kΩ, 1 W current-limiting resistor
3 -
Key or push button “Test/Reset” switch
(4 A at 24 VDC)
2 -
Red "ALARM LED" (15 mA at 24 VDC)
4 -
Green “Pilot” LED (15 mA at 24 VDC)
Black (-)
Red (+)
1
4
3
Black (-)
Red (+)
1
2
17
16
20
16
18
19
3
Standby Current
20 mA at 24 VAC
13 mA at 24 VDC
8 mA at 230 VAC
Alarm Current
95 mA at 24 VAC
60 mA at 24 VDC
15 mA at 230 VAC
Alarm Relay Contact Rating
10 A maximum at 250 VAC resistive
Trouble Relay Contact Rating
10 A maximum at 250 VAC resistive
Sensitivity Range (Factory Set)
1.5%/ft to ~2.75%/ft (4.8%/m to ~ 8.7%/m)
Differential
Pressure
0.01 in. (0.25 mm) - 1 in. (3 cm) of water
Air Velocity
300 ft/min to 4000 ft/min (91 m/min to 1219 m/
min)
Ambient Temperature
+32°F to +120°F (0°C to +49°C )