background image

6

en | Wiring

High-Voltage Conventional Duct Detector

F.01U.035.635

 | 5.0 | 201

1.09                                                      I

nstallation Guid

e                                           B

osch Security Systems, Inc.

3.3

Assembling the Intake Sampling Tubes

The intake sampling tube is a piece of steel piping with a series of holes drilled along its entire 

length. Ensure the holes face into the airflow. Exhaust tubes are pieces of steel piping 

approximately 7.5 in. (19 cm) long. The sampling tubes come in the standard lengths shown in 

the table. You need to cut them to fit in the duct.

Table 3.1

Intake Sampling Tube Standard Lengths

1.

Prepare the intake sampling tubes by cutting them to the desired lengths.

2.

Insert the stopper, included in the Installation Kit, into the end of the intake sampling 

tube.

3.4

Mounting the Intake Sampling Tubes

The intake sampling tube connectors are equipped with set screws that allow you to mount 

the tubes only in the directions shown in 

Figure 3.2

 on page 5. Consider the airflow direction 

when orienting the intake sampling tubes.

1.

Insert the intake sampling tubes and exhaust tubes into the connectors.

2.

Align the set screws to the set screw holes in the tubes and tighten.

Refer to 

Figure 3.1

 on page 5 for mounting details.

3.5

Mounting the Detector

1.

Position the detector and intake sampling tube assembly in the desired location.

2.

Using four duct mounting screws (four #12 x ½ in. [1.27 cm] sheet metal screws included 

in the installation kit), attach the D300A-HV on the duct.

3.6

Verifying the Air Sampling

Use a Dwyer Model 4000 Differential Pressure Gauge or its equivalent to verify the correct air 

sampling. Ensure the pressure differential between the input sampling tube and exhaust tube 

is greater than 0.01 in. (0.3 mm) and less than 1.2 in. (3.1 cm) of water.

Refer to 

Figure 3.2

 on page 5 for the intake sampling tube orientation to air flow direction.

4

Wiring 

Wiring must conform to applicable local codes, ordinances, and regulations covering this type 

of device. Wire the detectors according to the engineering drawing for that particular job 

requirement. For D300A-HV wiring details, refer to Figures 4.1 on page 7. Terminals are 

suitable for up to 14 AWG (1.8 mm) wire.

Model Number

Sampling tube length

FAA-325-2.5

2.5 ft (76 cm)

FAA-325-5

5 ft (152.5 cm)

FAA-325-10

10 ft (305 cm)

NOTICE! 

Ensure that power is removed from all wiring before routing.

Observe polarity.

CAUTION! 

Do not use looped wire under Terminals. Run break wire to provide supervision of 

connections.

Summary of Contents for D300A-HV

Page 1: ...High Voltage Conventional Duct Detector D300A HV en Installation Guide ...

Page 2: ......

Page 3: ...ble of Contents 1 Notice 4 2 Overview 4 3 Mounting 4 3 1 Preparing the Duct 4 3 2 Verifying Air Flow and Direction 5 3 3 Assembling the Intake Sampling Tubes 6 3 4 Mounting the Intake Sampling Tubes 6 3 5 Mounting the Detector 6 3 6 Verifying the Air Sampling 6 4 Wiring 6 4 1 Testing 8 4 2 Replacing the Detector Head 8 5 Specifications 8 ...

Page 4: ... 3 Mounting 3 1 Preparing the Duct When preparing the duct refer to Figure 3 1 on page 5 1 Remove the paper backing from the mounting template included in the Installation Kit 2 Attach the template to the duct at the desired location 3 Using the template as a guide drill four mounting holes 3 32 in 2 38 mm diameter for the duct mounting screws four 12 x in 1 27 cm sheet metal screws packaged in in...

Page 5: ...ientation to air flow direction Figure 3 1 Mount the Duct Housing Figure 3 2 Intake Sampling Tube Orientation 1 Six duct widths minimum from any bend or other obstruction 7 Exhaust tube 2 Air duct 8 Set screws 2 3 Template 9 Intake sampling tube connectors 2 4 Stopper 10 Duct mounting screws 2 5 Air flow for this illustration 11 Top of the D300A HV Housing 6 Intake sampling tube 1 Insert stopper a...

Page 6: ... tubes and tighten Refer to Figure 3 1 on page 5 for mounting details 3 5 Mounting the Detector 1 Position the detector and intake sampling tube assembly in the desired location 2 Using four duct mounting screws four 12 x in 1 27 cm sheet metal screws included in the installation kit attach the D300A HV on the duct 3 6 Verifying the Air Sampling Use a Dwyer Model 4000 Differential Pressure Gauge o...

Page 7: ...Wiring the D300A to an FACP 1 Switche Power connections upon reset connect items 2 or 3 not both 5 Alarm contacts 1 A at 24 VDC 2 230 VAC 60 Hz input at 0 1 A maximum 6 Trouble contacts 10 A at 115 VAC 3 24 VAC VDC 60 Hz input at 0 1 A maximum detector only Up to 1 9 A for auxiliary outputs 7 Remote accessories 4 Alarm contacts 10 A at 115 VAC Trouble contacts are shown in non energized condition ...

Page 8: ...ectric Smoke Detector Head 1 Remove the four screws holding the detector s cover 2 Remove the existing detector head by twisting it counterclockwise 3 Insert the D282A DH and turn it clockwise 4 Replace the detector s cover and tighten the screws 5 Specifications 1 1 2 kΩ 1 W current limiting resistor 3 Key or push button Test Reset switch 4 A at 24 VDC 2 Red ALARM LED 15 mA at 24 VDC 4 Green Pilo...

Page 9: ...urity Systems Inc Installation Guide F 01U 035 635 5 0 2011 09 Humidity 10 RH to 85 RH non condensing Intake Sampling Tubes FAA 325 2 5 2 5 ft 0 8m FAA 325 5 5 0 ft 1 5m FAA 325 10 10 ft 3m Replacement Detector Head D282A DH Replacement Photoelectric Smoke Detector Head ...

Page 10: ...10 en Specifications High Voltage Conventional Duct Detector F 01U 035 635 5 0 2011 09 Installation Guide Bosch Security Systems Inc ...

Page 11: ......

Page 12: ...Bosch Security Systems Inc 130 Perinton Parkway NY 14450 Fairport USA www boschsecurity us Bosch Security Systems Inc 2011 ...

Reviews: