High-Voltage Conventional Duct Detector
Wiring | en
7
Bosch Security Systems, Inc.
Installation Guide
F.01U.
035
.635
| 5.0 | 2011.09
To wire the D300A-HV:
1.
De-energize the power source.
2.
Wire all connections according to the engineering drawings.
3.
Verify the system wiring.
4.
Energize the detector.
Figure 4.1
Wiring the D300A Terminals
Figure 4.2
Wiring the D300A to an FACP
1 -
Switche Power connections upon
reset(connect items 2 or 3, not both)
5 -
Alarm contacts 1 A at 24 VDC
2 -
230 VAC 60 Hz input at 0.1 A
maximum
6 -
Trouble contacts 10 A at 115 VAC*
3 -
24 VAC/VDC 60 Hz input at 0.1 A
maximum (detector only). Up to 1.9 A
for auxiliary outputs.
7 -
Remote accessories
4 -
Alarm contacts 10 A at 115 VAC
* Trouble contacts are shown in non-energized condition. Trouble contacts monitor power
connected and head removed.
1 -
UL Listed FACp
3 -
EOL Device
2 -
D300A-HV Detector
1
3
15
14
15
14
11
11
12
12
2
2