Heating circuit data
|
33
6 720 802 836 (2012/05)
CFB 840
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 48 Setting the external changeover
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.24 External fault message - pump
This function is turned off at in factory setting.
This menu item determines whether fault messages relating to a pump
should be displayed.
You may connect an external volt free fault contact to terminals WF1 and
WF2. A fault message will be displayed if the contact is open.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
External fault
message pump
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 49 External fault message - pump
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.25 Screed drying
If the heating system comprises underfloor heating, this control unit a
drying program for the screed can be entered. As heating system
Under-
floor
must be set.
After a power failure, screed drying continues from where it was
interrupted.
Fig. 50 Screed drying
[x]
Time (days)
[y]
Temperature
[a]
3 days' hold time
[b]
Temp increase by
[c]
max. temperature
[d]
Setback by
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Screed drying
appears.
Input range
Factory setting
External day/night/aut none
day via WF1/3
via WF1/2/3
none
Table 63 Setting range External changeover
Terminals WF1 / 2 / 3 of the control unit can be used in
either of the areas DHW, heating circuit 1 or heating
circuit 2.
If under menu option
External day/night/aut via WF1/
2/3
has been entered, this menu item cannot be called
up since the input contact is already allocated
HEAT CIRC. DATA 2
External
Day/night/aut
via WF1/2/3
6 720 802 836-62.1TL
HEAT CIRC. DATA 2
External fault
message pump
via WF1/2
6 720 802 836-63.1TL
Input range
Factory setting
External fault
message pump
none
via WF1/2
none
Table 64 Setting range External fault message - pump
Check with your screed contractor for special
requirements for screed drying prior to enabling this
function.