32
|
Heating circuit data
CFB 840
6 720 802 836 (2012/05)
10.21 Set the actuator run-time
This parameter determines the run-time of the existing actuators. Most
actuators have a runtime of 120 s.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Actuator run time
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 46 Set the actuator run-time
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.22 Setting the Boiler raising
If the temperature in a heating circuit is controlled with a mixing valve, a
higher set value should be set for the boiler, than the normal set value for
the heating circuit.
The value
Boil. raising
corresponds to the temperature differential
between the set boiler temperature and the set heating circuit
temperature.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Boil. raising
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 47 Setting the Boiler raising
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.23 Setting the external changeover
Either of the following two changeover functions can be selected:
•
1. changeover
Day/night via the terminals WF1 and WF3
–
Contact WF1 and WF3 closed = day mode
–
Contact WF1 and WF3 open = night mode
•
2. changeover
day/night/aut via terminals WF1, WF2, WF3
–
Contact WF1 and WF3 closed = day mode
–
Contact WF1 and WF2 closed = night mode
–
all contacts open = automatic mode
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
External day/night/aut
appears.
If a constant oscillation of the mixing valve is noticeable,
slow down the control characteristics by reducing the
actuator runtime. Then the constant cycling of the mixing
valve should stop.
Input range
Factory setting
Actuator run time
10 sec – 600 sec
120 s
Table 61 Setting range Actuator runtime
HEAT CIRC. DATA 2
Actuator
run time
90sec
6 720 802 836-60.1TL
Input range
Factory setting
Boil. raising
0 °C – 20 °C
5 °C
Table 62 Setting range Boiler raising
Menu item
External changeover
is only displayed if
under menu option
Remote control
–
none
has been
selected and control unit CFB 840 is installed.
The menu item is also not shown if heating system
Room
thermostat
is selected since this requires a remote
control to be installed.
Terminals WF1 / 2 / 3 of the control unit can be used in
either of the areas DHW, heating circuit 1 or heating
circuit 2.
Activation
2. Changeover
is only possible if terminals
WF1 and WF2 via the
External fault message - pump
are not allocated.
Day mode will run constantly if both contacts are
simultaneously closed.
HEAT CIRC. DATA 2
Boil.raising
10
6 720 802 836-61.1TL
C