40
|
DHW data
CFB 840
6 720 802 836 (2012/05)
Fig. 69 Setting range Daily heat-up
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
11.11 DHW circulation pump
11.11.1 Selecting the DHW circulation pump
The function
DHW circulat.
ensures that DHW is immediately available
at the draw-off points.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
DHW
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
DHW Circulat.
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 70 Selecting the DHW circulation pump
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
11.11.2 Setting intervals
Operation in intervals saves operating costs for the circulation pump.
The function
DHW circulation per hour
ensures that DHW is
immediately available at the draw-off points.
The set interval applies during the period when the time program
enables the DHW circulation pump. This comprises:
•
The factory-set DHW circulation pump program
•
Your own DHW circulation pump program
•
A connection to the heating circuit switching times.
In constant mode the DHW circulation pump operates continuously
when in day mode, and is switched off in night mode.
Example
A proprietary time programme was entered that, within the period of
05:30 hours – 22:00 hours and when setting
DHW circulation is
enabled, turns on the
circulation pump 2 times per hour.
The circulation pump is enabled in cycles:
•
at 05:30 h for 3 minutes
•
at 06:00 h for 3 minutes
•
at 06:30 h for 3 minutes
•
etc., until 22:00 hours
Setting intervals
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
DHW
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
DHW Circulat. per hour
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 71 Setting intervals
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
If the DHW was heated to 60 °C within the last 12 hours,
it is not heated at the specified time.
Input range
Factory setting
Daily Heat-up
inactive
00:00 – 23:00 hours
Inactive
Table 85 Setting range Daily heat-up
Input range
Factory setting
DHW Circulat.
yes
no
yes
Table 86 Setting range DHW circulation
DHW Data
Daily
Heat-up
18:00
6 720 802 836-89.1TL
DHW Data
DHW Circulat.
no
6 720 802 836-90.1TL
Input range
Factory setting
DHW Circulat.
per hour
Off
1 time on
2 times on
3 times on
4 times on
5 times on
6 times on
Const. operation
2 times on
Table 87 Setting range DHW circulation per hour
DHW Data
DHW Circulat.
per hour
off
6 720 802 836-91.1TL