Special parameter
|
41
6 720 802 836 (2012/05)
CFB 840
12
Special parameter
This parameter enables Bosch service engineers to optimise the system
beyond the standard parameters by fine-tuning the sub-parameters.
This level is reserved for Bosch service engineers. Therefore, settings
are not made in plain text but in code. These are explained in a separate
document.
13
Heating curve
With menu
Heating curves
the current heating curves of all heating
circuits can be displayed.
The flow temperatures (VL), which depend on the outside temperature
(AT), are displayed.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
HEATING CURVE
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial to display the heating curves of all heating circuits.
Fig. 72 Heating curve
B
Press
Back
to return to the next higher level.
14
Relay test
Menu
Relay test
provides a check whether the external components
(e.g. pumps) are working correctly.
The display depends on which modules are installed. Depending on the
current operating conditions, there may be a time delay between
demand and display.
With the modules used most commonly in the control units, the following
relays can be called up:
•
Boiler
–
Burner
–
Actuator
–
Boiler pump (if enabled)
•
Heating circuit 0 – 4
–
Circulation pump
–
Actuator (not on heating circuit 0)
•
Domestic hot water
–
Cylinder primary pump
–
DHW circulation pump
Relay test example
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Relay test
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Heating circ. 2
appears.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Actuator
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 73 Relay test
B
Release
Display
to save your input.
B
Press
Back
twice to return to the next higher level.
The relay test is terminated.
15
Carrying out an LCD test
With menu
LCD test
it can be checked whether all signs and symbols are
fully displayed.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
LCD test
appears.
B
Press button
Display
.
The LCD is OK, when all symbols are correctly displayed.
B
Press
Back
to return to the next higher level.
CAUTION:
System damage through disabled functions!
The supply of heat to the heating system is not
guaranteed during the relay test. The control system
disables all functions.
B
Function
Relay test
must be stopped at the end of the
test to prevent damage to the system.
HEATING CURVE
Heating circ. 2
OT: 10 / 0 / -10
VL: 45 / 62 / 75
6 720 802 836-93.1TL
At the end of the Relay test, all settings are cancelled.
RELAY TEST 2
Heating circ. 2
Actuator
closed
6 720 802 836-94.1TL