Heating circuit data
CFB 840
6 720 802 836 (2012/05)
10.5 Setting the Minimum flow temperature
The minimum flow temperature limits the heating curve to a minimum
set value.
Change value only if necessary.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Minimum flow temp.
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 30 Setting the Minimum flow temperature
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.6 Setting the maximum flow temperature
The maximum flow temperature limits the heating curve to a maximum
set value.
Change value only if necessary.
B
Call up the service level.
GENERAL PARAM.
appears as the first main menu.
B
Turn the rotary dial until main menu
Heat.circuit
+ No. is displayed.
B
Press
Display
to call up a submenu.
B
Turn the rotary dial until submenu
Maximum flow temp.
appears.
B
Hold down button
Display
and turn the rotary dial until the required
value is shown.
Fig. 31 Setting the maximum flow temperature
B
Release
Display
to save your input.
B
Press
Back
to return to the next higher level.
10.7 Select the remote control
Under this menu item, it can be determined whether a remote control
will be installed for the heating circuit concerned. Here you can select
the following:
•
No remote control
•
Remote control with display (Programmer) "MEC heat. circ."
•
Remote control without display (BFU or BFU/F)
A remote control unit must be installed to enable the following functions,
which monitor the room temperature:
•
Night setback with hold room temperature
•
Max. room influence
•
Automatic adaptation
•
Optimisation
•
Heating system
Room controller
Input range
Factory setting
Design temp.
30 °C – 90 °C
75 °C for radiator/
convector/low end/
constant
45 °C for underfloor
heating
Table 41 Setting range Design temperature
If the heating system
Constant
is selected, this
parameter cannot be adjusted.
This value sets the temperature below which the flow
temperature must not drop.
Input range
Factory setting
Minimum
Flow temp.
5 °C – 70 °C
5 °C
Table 42 Setting range Minimum flow temperature
If the heating system
Constant
is selected, this
parameter cannot be adjusted.
HEAT CIRC. DATA 2
Minimum
Flow temp.
10
6 720 802 836-44.1TL
C
o
Input range
Factory setting
Maximum
Flow temp. for
underfloor heating
30 °C – 60 °C
50 °C
Maximum
Flow temp. for
radiators, convector
heaters, base point
30 °C – 90 °C
75 °C
Table 43 Setting range Maximum flow temperature
This value sets the temperature above which the flow
temperature must not rise.
For the heating circuit system
Constant
or when
External changeover
has been enabled, no remote
control unit may be installed.
HEAT CIRC. DATA 2
Maximum
Flow temp.
60
6 720 802 836-45.1TL
C
o