56
en | Connection
AUTODOME inteox 7000i - 2MP (pendant)
2020-07 | 1.0 |
Installation Manual (pendant)
Bosch Security Systems
AUTODOME Programmed N.O.S.
Contact
Alarm Condition
Open
Normal
Closed
Alarm
Cut or break
Tamper
Configuring a Normally Closed Supervised Alarm
1.
Install a 2.2 K end-of-line resistor in the alarm circuit.
2.
Connect the alarm wires to input 1 or 2 (pin 5 or 6) and to the ground (pin 7) at the
camera.
2.2K
Figure 13.3:
N.C.S. - Normally Closed Supervised Connections
1
Dry Contact
3
Dome Connector
2
Alarm 1 or 2 only (Pin 5 or 6)
4
Ground (Pin 7)
3.
From
Configuration
, select
Interfaces
>
Alarm Inputs
, select the number of the
Alarm
input
and finally, select N.C. See the table below for contact and condition details.
AUTODOME Programmed N.C.S.
Contact
Alarm Condition
Open
Alarm
Closed
Normal
Short
Tamper
Configuring Non-supervised Alarms (inputs 3 through 7)
You can configure alarms 3 through 7 as non-supervised Normally Open (N.O.) or Normally
Closed (N.C.) alarms.
Configuring a Normally Open Non-supervised Alarm
1.
Connect the alarm to the appropriate input (3 through 7) and ground at the camera.
Figure 13.4:
N.O. - Normally Open Non-supervised Connections
1
Dry Contact
3
Dome Connector