2000 Series |
Program Entry Guide | 4.0
Receiver
EN
| 15
Bosch Security Systems | 7/05 | 35114F
4.0 Receiver
4.1 Modem
Reports
1 Rcvr Format
Default:
Modem
Selection:
Modem, Pulse
0 Pulse
1 Modem
Set
Rcvr Format
to Modem to transmit reports in Modem II format with its advanced reporting capabilities.
You need firmware revision 8.00 or greater installed in your D6500 Receiver.
Table 2 shows the reports available.
The D6500 line card ack tone table must contain “Modem II for D9112.” Refer to the 6500: Line Program Entry
Guide.
Set
Rcvr Format
to Pulse to transmit in 4x2 Pulse Format. Be sure to program codes for each report group. Refer
to the
Section
4.2
Pulse Report Groups.
Table 2: Modem II Reports Chart
Modem II Report
Description
AC FAILURE
No AC power to system. Control panel runs on battery.
AC RESTORE
AC Power is restored to normal.
ALARM REPORT POINT
001 (-099)
Alarm Report from Points 1 to 24 or from an A, B, C, key. Refer to Section 7.0 ABC Keys for
instructions on setting reports from the keys.
ALARM REPORT
RECENT CLOSING
ID=001
POINT=001(24)
If an alarm occurs within 2 minutes of a Closing event, the system sends an Alarm Recent
Close Report.
ALARM CROSS POINT
001 (-099)
Alarm Report from Points 1 to 24 with point code for Cross or Partner point.
The ALARM RECENT CLOSE message overrides the ALARM CROSS POINT message.
The ALARM EXIT ERROR message does not apply to Cross, Partner, Double Knock, or Alarm
Verification points
BATTERY LOW
System battery is low.
BATTERY MISSING
System battery is disconnected. Battery must be missing for 60 seconds.
BATTERY RESTORE
Missing or low battery is restored.
CANCEL REPORT
Cancel Report from keyswitch.
CANCEL REPORT ID
001 (-008)
Cancel Report with user ID for users 1 to 8.
Summary of Contents for 2000 Series
Page 1: ...EN Program Entry Guide Control Panels 2000 Series ...
Page 14: ...2000 Series Program Entry Guide 3 0 Reports EN 14 Bosch Security Systems 7 05 35114F Notes ...
Page 26: ...2000 Series Program Entry Guide 6 0 Open Close EN 26 Bosch Security Systems 7 05 35114F Notes ...
Page 30: ...2000 Series Program Entry Guide 8 0 Bell EN 30 Bosch Security Systems 7 05 35114F Notes ...
Page 58: ...2000 Series Program Entry Guide 14 0 User Test EN 58 Bosch Security Systems 7 05 35114F Notes ...