2000 Series |
Program Entry Guide | 11.0
Point Codes
EN
| 43
Bosch Security Systems | 7/05 | 35114F
11.2 Digit 2, Alarm Responses
Table 6: Digit 2 Selections
0 1 2 3 4 5 6 7 8 9
No Alarm Response
: Set Digit 2 to 0 (zero) only if you want no alarm response for
this point.
Note:
Set Digit 2 to 0 if you are using this point number for an RF Keypad or arming device.
X
Reports
: Points send Alarm, Cancel, Trouble, Bypass, Swinger Bypass, and Restoral
Reports as programmed. Bypass Reports are only sent with Closing Reports.
X X X X X X X X
Alarm Report Delay:
If a user enters their passcode to silence an alarm before the
programmed Alarm Report Delay time expires, the alarm is canceled. No Alarm,
Cancel, or Restoral Report is sent. Program
Delay Alrm Rpt
in Section 3.0 Reports
to determine the duration of the delay.
•
Voice Active Function
: When the
Delay Alrm Rpt
prompt is set to 255, Alarm
Report Delay points (Digit 2 = 2, 3, 7, or 8) begin the 2-way Voice Verification
process. Refer to
Delay Alrm Rpt
in Section 3.0 Reports.
•
Duress Reports and A, B, C Key Reports are
not
affected by the Alarm Report
Delay. These reports are sent immediately in all cases.
X X
X X
Swinger Bypass:
The
Swinger Count
prompt in the System Configuration Group
sets the swinger count for this Swinger Bypass point option. When the number of
alarms or troubles in an armed or disarmed period reaches the swinger count, the
system automatically bypasses points programmed for Swinger Bypass. Turning the
system off clears the bypass. If a 24-hour point swinger bypasses while the system is
off, turning the system on (starting exit delay) and then turning the system off
(pressing [CLEAR]) clears the bypass. Swinger bypass is a point trouble and
activates the Point Trouble Relay function.
When a point is swinger bypassed, the Point Trouble Relay is activated.
X
X
X
X
Alarm Output
: Points programmed for alarm output provide output at Terminals 4
and 5 as part of the alarm response. Fire points provide a pulsed output. Non-Fire
points provide a steady output. Output lasts for the duration programmed in
Bell
Time
. Fire output always takes precedence over non-fire output.
X X X X X
Summary of Contents for 2000 Series
Page 1: ...EN Program Entry Guide Control Panels 2000 Series ...
Page 14: ...2000 Series Program Entry Guide 3 0 Reports EN 14 Bosch Security Systems 7 05 35114F Notes ...
Page 26: ...2000 Series Program Entry Guide 6 0 Open Close EN 26 Bosch Security Systems 7 05 35114F Notes ...
Page 30: ...2000 Series Program Entry Guide 8 0 Bell EN 30 Bosch Security Systems 7 05 35114F Notes ...
Page 58: ...2000 Series Program Entry Guide 14 0 User Test EN 58 Bosch Security Systems 7 05 35114F Notes ...