User’s Manual
35
5.2.2. C
APACITOR
T
ESTING
P
ROCEDURE
1. Open the panel door to expose the capacitor bank.
1. Measure voltage across each cap and make note for future reference.
2. Any voltage difference more than 15% indicates a substantial change in
capacitance.
Example: DC bus = 540V, each series cap = 270V
15% of 270 = 40.5V
cap 1 = 290V
cap 2 = 250V
Turn off power, discharge the capacitor bank voltage and replace both
capacitors if the difference is more than 15%.
5.2.3. C
LEANING
It may be necessary to clean off dust, debris, or chemical build-up on high
voltage bus bars or other exposed components. If cleaning is needed:
•
Remove power and allow all voltages to drain.
•
Check for residual voltages with meter.
•
Clean affected areas with rag, brush or denatured alcohol, depending on
the type of contamination.
•
Once area is clean and dry, reapply power.
5.2.4. H
EATSINKS
Dirt can build up on heatsink surfaces degrading its ability to dissipate heat.
The heatsinks should be checked for large amounts of deposits and cleaned
as needed. The maintenance interval depends upon the amount of activity and
the environment inside the cabinet.
Checking the heatsink should be included when checking for fan operation.
Summary of Contents for M3460UC
Page 6: ...M3460 6 This page intentionally left blank ...
Page 18: ...M3460 18 Figure 3 2 M3460UC POWER Terminal connection ...
Page 38: ...M3460 38 This page intentionally left blank ...
Page 43: ...User s Manual 43 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Page 44: ...M3460 44 Figure 6 3 M3460 E4 Enclosure Dimensional Outline ...
Page 52: ...M3460 52 This page intentionally left blank ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3460 54 This page intentionally left blank ...