User’s Manual
39
6.
E
NGINEERING
D
ATA
6.1. R
ATINGS
Table 6-1: M3460 kW Ratings
DC
B
US
C
URRENT
(A
MPS
)
230VAC
S
YSTEM
V
OLTAGE
380-415VAC
S
YSTEM
V
OLTAGE
460VAC
S
YSTEM
V
OLTAGE
85 A
25 kW
43 kW
50 kW
127 A
38 kW
65 kW
75 kW
170 A
50 kW
87 kW
100 kW
255 A
75 kW
130 kW
150 kW
340 A
100 kW
175 kW
200 kW
425 A
125 kW
215 kW
250 kW
Table 6-2: Factory Setpoints for DC Bus Threshold and Test Boost Voltages
S
YSTEM
V
OLTAGE
DC
B
US
T
HRESHOLD
T
EST
B
OOST
230 VAC
285 VDC
+50 VDC
380
– 415 VAC
485 VDC
+100 VDC
460 VAC
585 VDC
+100 VDC
Table 6-3: M3460 Minimum Input Voltages
S
YSTEM
V
OLTAGE
M
INIMUM
DC
I
NPUT
V
OLTAGE
(IUV
L
EVEL
)
M
INIMUM
DC
I
NPUT
R
EQUIRED FOR
P
RECHARGE
C
OMPLETE
(PCC)
230 VAC
160 VDC
270 VDC
380
– 415 VAC
265 VDC
445-487 VDC
460 VAC
320 VDC
540 VDC
Minimum AC input power required after PCC for full power operation with energy storage.
Minimum DC input required after PCC for full power operation with energy storage.
Summary of Contents for M3460UC
Page 6: ...M3460 6 This page intentionally left blank ...
Page 18: ...M3460 18 Figure 3 2 M3460UC POWER Terminal connection ...
Page 38: ...M3460 38 This page intentionally left blank ...
Page 43: ...User s Manual 43 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Page 44: ...M3460 44 Figure 6 3 M3460 E4 Enclosure Dimensional Outline ...
Page 52: ...M3460 52 This page intentionally left blank ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3460 54 This page intentionally left blank ...