5.3. T
ROUBLESHOOTING
Below are suggestions on how to check some common issues.
If you continue to have problems after going over this list, please contact Bonitron.
Table 5-1: Troubleshooting Guide
S
YMPTOM
A
CTION
No lights are ON
▪
Check incoming power.
Ride-Thru will not
become active
▪
Check Enable Input.
▪
Check input and output fuses.
Test Mode Does Not
Raise Output Voltage
▪
Check Enable Input.
▪
Check Test Input.
▪
Check input and output fuses.
▪
Check threshold voltage setting.
Stays in Test Mode
▪
Check Test Input.
Ride-Thru Ready light is
OFF or Ride-Thru Ready
output is open
▪
Check Enable Input.
▪
Check IGBT fuses.
Precharge Complete
light is OFF or
Precharge Complete
output is open
▪
Check Enable Input.
▪
Check Drive Bus voltage level.
Voltage Fault output is
open
▪
Check input fuses.
▪
Check Drive Bus level.
Overtemperature output
is open
▪
Check jumpers on 3460M6 board.
▪
Check threshold voltage setting.
General Fault output is
open
▪
Check Ride-Thru Ready output
▪
Check Voltage Fault output
▪
Check Overtemperature output
Ride-Thru Active output
is closed when Ride-
Thru is not active
▪
Check Drive Bus voltage.
▪
Check threshold voltage setting.
▪
Check jumpers on 3460M6 board.
Summary of Contents for M3460UC
Page 6: ...M3460 6 This page intentionally left blank ...
Page 18: ...M3460 18 Figure 3 2 M3460UC POWER Terminal connection ...
Page 38: ...M3460 38 This page intentionally left blank ...
Page 43: ...User s Manual 43 Figure 6 2 M3460 E2 Enclosure Dimensional Outline ...
Page 44: ...M3460 44 Figure 6 3 M3460 E4 Enclosure Dimensional Outline ...
Page 52: ...M3460 52 This page intentionally left blank ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3460 54 This page intentionally left blank ...