User’s Manual
33
6.
E
NGINEERING
D
ATA
6.1. R
ATINGS
C
HARTS
Table 6-1: Model M3534R Ride-Thru Module Ratings
M
ODEL
N
UMBER
AC
I
NPUT
M
AX
.
O
UTPUT
P
OWER
R
ECOMMENDED
F
USE
R
ATINGS
(AC
I
NPUT
/
DC
O
UTPUT
)
M
AX
DC
O
UTPUT
C
URRENT
C
HX
S
IZE
M3534R-L012-K7
230VAC 12kW /16hp
A60Q40-2 / A70QS50-14F
40ADC
K7
M3534R-L025-A9
230VAC 25kW /33hp
A60Q125 / A60Q80
85ADC
A9
M3534R-E020-K7
400VAC 20kW /26hp
A60Q40-2 / A70QS50-14F
40ADC
K7
M3534R-E043-A9
400VAC 43kW /57hp
A60Q125 / A70Q80
85ADC
A9
M3534R-H024-K7
460VAC 24kW /32hp
A60Q40-2 / A70QS50-14F
40ADC
K7
M3534R-H050-A9
460VAC 50kW /67hp
A60Q125 / A70Q80
85ADC
A9
The codes listed in the
CHX SIZE
column of the table above refer to specific Bonitron chassis
designs. For chassis details see the dimensional outlines in Section 6.4.
For higher ratings, batteries can be added and 85 Amp units can be paralleled.
Table 6-2: Model M3534R Ride-Thru Module Voltage Levels
AC
I
NPUT
V
OLTAGE
DC
B
US
V
OLTAGE
L
EVELS
T
HRESHOLD
M
IN AT
F
ULL
L
OAD
N
OMINAL
208VAC
265VDC
255VDC
290VDC
230VAC
285VDC
275VDC
320VDC
380 / 400 / 415VAC
485VDC
475VDC
565VDC
460VAC
585VDC
575VDC
640VDC
The
Min at Full Load
column in the table above lists the minimum voltage level at which the DC
bus will be maintained when the RTM is active. This is usually about 90% of the nominal DC bus
level, and 7-10V
below the THRESHOLD where “activity” begins.
The
NOMINAL
column in the table above lists the normal operating DC bus voltage level.
6.2. W
ATT
L
OSS
S
TANDBY
M
ODE
Less than 25 watts for 40A units
Less than 25 watts for 85A units
Approximately 3 watts for DP Series panels
B
OOST
M
ODE
All units are 95% efficient or better at full load.