User’s Manual
5
2.3. G
ENERAL
S
PECIFICATIONS
Table 2-2: General Specifications Chart
P
ARAMETER
S
PECIFICATION
AC Input Voltage
208 - 480VAC
DC Output Voltage
265 - 585VDC minimum
295 - 650VDC nominal
Max. DC Output Current
40A
– 85A
Maximum Kilowatt Rating
24kW
– 50kW
Maximum Sag Duration
2 seconds
Duty Cycle Rating
1% duty rated at 50% voltage with 100% load
Pre-charge Time
Less than 100 milliseconds
Inactive Power Usage
Less than 25W
Fault / Status Indicators
Power (PWR)
Overtemp (OT)
Ride-Thru Active (RTA)
Ride-Thru Ready (RTR)
Power Connections
3-Phase AC Line Input, Ground
DC Bus Output
External Energy Reservoir or Bus Support Module
Control Inputs
24V input initiates TEST cycle
24V input disables BOOST mode
Status Outputs
OT relay contacts available on all models
RTA relay contacts available on all models
Operating Temp.
40°C
Storage Temp
-20°C to +65°C
Humidity
Below 90% non-condensing
Atmosphere
Free of corrosive gas and conductive dust