M3534R 40&85A
20
Table 4-4
: Status Signal Component Details for Models with DP10 “I3” Option
B
OARD
S
TATUS
C
OMPONENTS
S
TATUS
S
IGNAL
C
OMPONENT
ID
R
IDE
-T
HRU
A
CTIVE
(RTA)
R
IDE
-T
HRU
R
EADY
(RTR)
3534I3
Jumper
J2
J1
Contact Ratings
120mA at 350VDC
120mA at 350VDC
Indicator
None
None
Interface Board
Terminations
3534I3
TB4-1,2
3534I3
TB4-3,4
Isolation
3kV
3kV
Table 4-5: Status Contact Logic Details
– R3 Control Board
RTM
S
TATUS
C
ONDITION
I
NDICATORS
J
UMPER
P
OSITIONS
&
C
ONTACT
S
TATES
PWR
OT
RTA
OT
(J2)
RTA
(J3)
(LD1) (LD2) (LD3)
N.C.
N.O.
N.C.
N.O.
Power off or P.S. failure
OFF
OFF
OFF
X
O
X
O
Power on & DC bus OK
ON
OFF
OFF
O
X
X
O
Power on & Overtemp
ON
ON
OFF
X
O
X
O
Power on & Ride-Thru Active
ON
OFF
ON
O
X
O
X
NOTES:
X = contact is closed under stated conditions
O = contact is open under stated conditions
4.2.2. I
NDICATORS
4.2.2.1. ASB
3534R3
RTM
C
ONTROL
B
OARD
The ASB 3534R3 is the main control board of the Ride-Thru Control
Module used in all M3534R Ride-Thru Control Modules built in the K7 or
A9 chassis type.