User’s Manual
19
F
OR
M
ODELS WITH
DP10
O
PTION
(I3
BOARD
)
Fault Signals are available on the 3534I3 board as described in Sec
4.2.2.4.
Table 4-1: Control Status Signal Connection Details for Standard Models
B
OARD
T
ERMINAL
T
YPE
F
UNCTION
E
LECTRICAL
S
PECIFICATIONS
M
IN
W
IRE
AWG
M
AX
W
IRE
AWG
T
ORQUE
LB
-
IN
3534R3
Phoenix plug TB5
Status
120VAC / .5 Amp
1kV Isolation
24VDC / 1 Amp
1kV Isolation
22
16
2 lb-in
Phoenix plug TB6
Test
24VDC / 20mA
1kV Isolation
22
16
2 lb-in
.20” Female Spade Lug
Disable
24VDC / 20mA
1kV Isolation
22
16
Table 4-2: Control Signal C
onnection Details for Models with DP10 “I3” Option
B
OARD
T
ERMINAL
T
YPE
F
UNCTION
E
LECTRICAL
S
PECIFICATIONS
M
IN
W
IRE
AWG
M
AX
W
IRE
AWG
T
ORQUE
LB
-
IN
3534I3
Phoenix plug TB4
Disable
15-24VDC / 20mA
3kV Isolation
22
16
2 lb-in
Table 4-3: Status Signal Component Details for Standard Models
B
OARD
S
TATUS
C
OMPONENTS
S
TATUS
S
IGNAL
C
OMPONENT
ID
O
VER
T
EMP
(OT)
R
IDE
-T
HRU
A
CTIVE
(RTA)
3534R3
Jumper
J2
J3
Contact Ratings
1A at 24VAC
0.5A at 115VAC
1A at 24VAC
0.5A at 115VAC
Indicator
LD2
LD3
Control Board
Terminations
3534R3
TB5-2,4
3534R3
TB5-3,4
Isolation
1kV
1kV
NOTE:
The 3534R3 Ride-Thru Control Board is used in all
K7
and
A9
chassis modules.