Profibus DP V1 Agile
06/2010
48
Handling of the Objects
16.4.3.2 Behavior in Quick Stop
In this, the parameters
Switch-off Threshold Stop Function
637 (percent of fmax) and
Holding Time
Stop Function
638 (holding time after falling short of the switch-off threshold) are relevant. In a quick
stop, the drive is shut down via the emergency stop ramps (
Emergency Stop Clockwise
424 or
Emergency Stop Antclockwise
425).
f
s
Start Quick Stop
OFF
change of state
t
Switch-off Threshold Stop Fct.
637
Emergency Stop Clockwise
424
425
Emergency Stop Anticlockwise
Holdig Time Stop Function
638
If the frequency/speed zero has been reached during the holding time, the drive continues to be
supplied with direct current until the switch-off time has expired. With this measure, there is an
assurance that the drive is stationary in a change of state.