Profibus DP V1 Agile
06/2010
38
Handling of the Objects
Note:
The displayed "PDP active current" depends on the control system. In field-orientation,
the torque-forming current is displayed, in applications with a v/f characteristic control,
the active current, which is also a measure for the torque.
The “PDP absolute current” (r.m.s. current) is always positive. Active current and torque-
forming current have a sign prefixed.
Positive currents = motor
Negative currents = generator operation.
Current Scaling
Standardization
Reference value
Binary
Decimal
Hexadecimal
+ 100%
+ 2
14
16384
0x4000
The possible range = ±200% = +32768 to -32768 = 0x8000 to 0x7FFF
For the internal scaling, the data set change-over capable parameter
Rated current
371 is used as a
reference.
Parameter
Setting
No.
Description
Min.
Max.
Factory Setting
371 Rated Current
0,01 · I
FUN
10 · I
FUN
I
FUN