Quick Start Guide ACT
77
GB
4.3.2
External 24 V power supply X210A.1 & X210A.2
NOTICE
Device damage possible
The digital inputs and the DC 24 V terminal of the electronic
control equipment can withstand external voltage up to DC 30 V.
Higher voltages may destroy the unit.
•
Avoid higher voltage levels.
•
Use suitable external power supply units with a maximum
output current of DC 30 V or use appropriate fuses to protect
the unit.
The bidirectional control terminals X210A.1/ X210A.2 can be used as a voltage
output or voltage input. By connecting an external power supply of DC
24 V ±10% to terminals X210A.1/X210A.2, the function of inputs and outputs
as well as the communication can be parameterized and maintained, even when
mains voltage is off.
Requirements to be met by external power supply
Input voltage range DC 24 V ±10%
Rated input current Max. 1.1 A
Peak inrush current Typically: < 25 A
External fuse
Via standard fuse elements for rated current, characteristic:
slow
Safety
Safety extra low voltage (SELV) according to EN 61800-5-1
4.3.3
Control terminal X10
Relay output X10
S3OUT Parameterizable relay output
Control terminal X10
Term.
Description
1 ... 3 Relay output, floating change-over contact, response time approx. 40 ms,
maximum contact load:
make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
break contact: AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
Summary of Contents for ACTIVE ACT2 Series
Page 1: ...Quick Start Guide 132 kW...
Page 2: ......
Page 3: ......
Page 4: ......
Page 13: ...12 20 Quick Start Guide ACT 11 I Grandezza 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 15: ...12 20 Quick Start Guide ACT 13 I Grandezza 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 62: ...60 Quick Start Guide ACT 12 20 GB Size 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 64: ...62 Quick Start Guide ACT 12 20 GB Size 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 112: ...110 Quick Start Guide ACT 12 20 D Baugr e 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 114: ...112 Quick Start Guide ACT 12 20 D Baugr e 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 161: ...12 20 Quick Start Guide ACT 159 F Taille constructive 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 163: ...12 20 Quick Start Guide ACT 161 F Taille constructive 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 212: ...210 Quick Start Guide ACT 12 20 E Tama o 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 214: ...212 Quick Start Guide ACT 12 20 E Tama o 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ...COD VEC 370 R4...