68
Quick Start Guide ACT
12/20
GB
Mains connection
The mains supply cable may be as long as required.
To be separated from control, data and motor
cable.
DC-link connection
The frequency inverter is to be connected to the
same mains potential or a common direct voltage
source. Cables with a length >300 mm must be
shielded, the cable shield must be connected to the
mounting plate on both sides. Use twisted cables
where possible.
Control connection
Control and signal cables must be kept physically
separate from the power cables. Analog signal lines
are to be connected to the shield potential on one
side. Install sensor cables separate from motor
cables.
The low voltage circuits (e.g. terminal X210A,
X210B) are isolated from the main circuit (e.g. U, V,
W) by way of safety isolation and safety impedance.
Motor and brake resistor
The shield of the motor cable is to be connected to
ground potential properly on both sides. On the
motor side use a metal compression gland. On the
frequency inverter side an appropriate shield clamp
is to be used. The signal cable used for monitoring
the motor temperature must be kept separate from
the motor cable. Connect the shield of this line on
both sides. If a braking resistor is used, the
connection cable must also be shielded, and the
shield is to be connected to earth potential on both
sides.
Relay
The relay allows using high-energy signals.
Line choke
Line chokes reduce mains harmonics and reactive power. In addition, a longer
service life of the frequency inverter is possible. When using a line choke, note
that line chokes may reduce the maximum output voltage of the frequency
inverter. The line choke must be installed between the mains connection and
the input filter.
A
B
C
D
Summary of Contents for ACTIVE ACT2 Series
Page 1: ...Quick Start Guide 132 kW...
Page 2: ......
Page 3: ......
Page 4: ......
Page 13: ...12 20 Quick Start Guide ACT 11 I Grandezza 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 15: ...12 20 Quick Start Guide ACT 13 I Grandezza 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 62: ...60 Quick Start Guide ACT 12 20 GB Size 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 64: ...62 Quick Start Guide ACT 12 20 GB Size 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 112: ...110 Quick Start Guide ACT 12 20 D Baugr e 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 114: ...112 Quick Start Guide ACT 12 20 D Baugr e 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 161: ...12 20 Quick Start Guide ACT 159 F Taille constructive 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 163: ...12 20 Quick Start Guide ACT 161 F Taille constructive 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 212: ...210 Quick Start Guide ACT 12 20 E Tama o 5 c c1 a a1 a2 x b b1 x x 100 mm...
Page 214: ...212 Quick Start Guide ACT 12 20 E Tama o 6 a a1 a2 x x 100 mm b b1 x c c1...
Page 255: ......
Page 256: ......
Page 257: ......
Page 258: ...COD VEC 370 R4...