3. ELECTRICAL & WIRING
EXTERNAL WIRING
FX PRO VS II In-Ground Pumps
MUST
be permanently connected to an appropriate electrical circuit.
If other lights or appliances are also on the same circuit, be sure to add their amp loads before
calculating wire and circuit breaker sizes. Use the load circuit breaker as the Master On-Off switch.
Always Install a Ground Fault Circuit Interrupter (GFCI) in circuit; it will sense a short circuit to ground
and disconnect power before it becomes dangerous to pool users. For size of GFCI required and
test procedures for GFCI, see manufacturer’s instructions. In case of a power outage, check GFCI for
tripping, which will prevent normal pump operation. Reset if necessary.
WARNING
All wiring must be done by a licensed electrician.
See specific wiring instructions in the Technical Data sections for each pump
covered by this manual.
Above Ground FX PRO VS II pump has pre-attached power cords with 3
prong grounded plugs. If local electrical codes call for power cords with twist
lock plugs, please check with your local professional pool store or online for
availability.
If you do not use conduit when wiring motor, be sure to seal wire opening on the back
end of the motor to prevent dirt, bugs, etc., from entering
NOTICE
NOTICE
Model # NE9881, 115V pump comes with a 3-ft, 3 prong grounded power cord attached.
Never use an extension cord to connect a pump with a pre-wired cord to the circuit. You
must bring a permanent outlet with GFCI protection to the location of the pump.
WIRING DIAGRAMS FOR NE9882, 230V PUMP
NOTICE
Never disconnect or change locations of any factory installed wires. This will result in
voiding your warranty.
WARNING
NEVER
open the motor housing to make changes to the factory installed
external power cord. If you attempt to do so it will void your warranty. If the
cord on the pump you purchased is not compatible with your local electrical or
building cords, you must return it to your retailer and purchase a different style
pump.