13
Model BD306 Dual-Input Pump Controller Instruction Manual
Return to Table of Contents
6.2. Panel Mounting Instructions
• Prepare a standard
⅛
DIN panel cutout – 3.622” x 1.772” (92 mm x 45 mm).
Refer to Figure 1 below, for more details.
•
Clearance: allow at least 6.0” (152 mm) behind the panel for wiring.
•
Panel thickness: 0.04” - 0.25” (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06”
(1.5 mm) steel panel, 0.16” (4.1 mm) plastic panel.
•
Remove the two mounting brackets provided with the meter (back-off the two
screws so that there is ¼” (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
• Insert meter into the panel cutout.
•
Install mounting brackets and tighten the screws against the panel. To achieve
a proper seal, tighten the mounting bracket screws evenly until meter is snug
to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
Note:
See Figure 23 on page 101 for 1/8 DIN Panel Cutout Template