70
Model BD306 Dual-Input Pump Controller Instruction Manual
Display
Parameter
Action/Setting
C Hi
Current High
Calibrate high current input (e.g. 20 mA)
U CAL
Voltage Calibration
Calibrate voltage input
U Lo
Voltage Low
Calibrate low voltage input (e.g. 0 V)
U Hi
Voltage High
Calibrate high voltage input (e.g. 10 V)
CoPy
Copy
Enter copy function
SEnd
Send
Send meter settings to another meter
donE
Done
Copy function completed
diAG
Diagnostics
Display parameter settings
7.13.2.
Noise Filter (
FiLtEr
)
The noise filter is available for unusually noisy signals that cause an unstable process variable
display. The noise filter averages the input signal over a certain period. The filter level deter-
mines the length of time over which the signal is averaged. The filter level can be set between 2
and 199. The higher the filter level, the longer the averaging time and so the longer it takes the
display to settle to its final value. Setting the filter level to zero disables the filter function.