75
Model BD306 Dual-Input Pump Controller Instruction Manual
Multi-Point Linearization (
L inEAr
)
Meters are set up at the factory for linear function with 2-point linearization. Up to 32 lineariza
-
tion points can be selected for PV1 under the linear function. The multi-point linearization can
be used to linearize the display for non-linear signals such as those from level transmitters used
to measure volume in odd-shaped tanks or to convert level to flow using weirs and flumes with
complex exponent.
Return to Table of Contents
Round Horizontal Tank Linearization (
rHt
)
This function is used to calculate volume in a round horizontal tank with flat ends. The volume is
calculated based on the diameter and length of the tank. The tank’s dimensions can be entered
in inches or centimeters; the meter automatically calculates the volume in gallons or liters. After
entering the dimensions, complete the scaling process with the display values calculated by the
meter. The meter can be re-scaled to display the volume in any engineering unit without the
need to re-enter the dimensions again.
Note: After Scale is displayed continue pressing the Enter button
until the meter completes the scaling of the input and display values.