KT-230-2
7
Select cable cross-sections according to local regulations!
Use copper cables with a sheath quality suitable for at least 85°C. Select cable
quality according to the place of installation, e.g., UV and/or oil resistant.
Available cable bushings into the module housing with fully equipped compressor
4FES-3(Y) .. 6FE-50(Y)
Screwed joints:
at least: 1 x M16x1,5, 2 x M20x1,5, 2 x M25x1,5
4PTE(U)-6(L)K ..
6CTE(U)-50(L)K
Screwed joints:
at least: 1 x M16x1,5, 2 x M20x1,5, 2 x M25x1,5
8GE-50(Y) .. 8FE-70(Y)
Screwed joints:
at least: 1 x M16x1,5, 2 x M20x1,5, 2 x M25x1,5
Blind caps: 4 x M63x1,5
Features of the compressor module
Enclosure class
Module housing in installed condition: IP65
Compressor module without module housing: IP00
The CM-RC-01 is used with 8-cylinder compressors 8GE-50(Y) .. 8FE-70(Y)
installed in the compressor connection box. Terminal box in the state of deliv-
ery: IP54
Internal electronic fuse
Terminal strips CN4 to CN6
This fuse protects the CM-RC-01 if a short-circuit occurs in one of the connec-
ted components: the oil heater, additional fan or a solenoid valve.
A warning is issued in the BEST SOFTWARE or via Modbus.
Place of installation
permitted ambient temperature: -30°C .. +70°C
permitted relative humidity: 5% .. 95% (EN60721-3-3 Class 3K3 and 3C3)
maximum permitted height above altitude 0: 2000 m
Electromagnetic compatibility
The compressor module meets the requirements of the EU EMC Directive
2014/30/EU
Interference immunity
EN61000-6-1:2007, immunity for residential, commercial and light-industrial
environments
EN61000-6-2:2005, immunity for industrial environments
Emitted interference
EN61000-6-3:2007+A1:2011, emitted interference for residential, commercial
and light-industrial environments
The compressor module supplies the internal power
supply for the peripheral devices (solenoid valves, any
additional fan, oil monitoring and the oil heater) and for
terminal strips CN7 to CN12.