Page 6

5.7

Adjusting the detector

5.8

Mounting height F+4

5.14

Crossing traffic masking CTM F + 5

5.15

Wide field B

5.9

Comfort functions C

The settings are identified as follows:

e.g.

D+…

Remote control menu

e.g.

P.1…

Primary programming mode with keys, function no. 1

e.g.

S.3…

Secondary programming mode with keys, function no. 3

F + 4 + 1…7

P.2+1…7 (keys)

1 = 2.0 bis 2.4 m

5 = 5.0 bis 5.9 m

2 = 2.5 bis 2.9 m

6 = 6.0 bis 6.9 m

3 = 3.0 bis 3.9 m

7 = 7.0 bis 7.9 m

4 = 4.0 bis 4.9 m

It is essential to adjust the mounting height if it does not match the
factory setting.

5.10

Field size D

D + 1…9

P.4+1…9 (keys)

Levels 1 (small field) to 9 (large field)
Refer to the technical data for field dimensions.

5.12

Direction recognition E+1

5.13

Relay parameter settings E+2

5.11

Relay hold interval F+1

F + 1 + 1…4

S.1 + 1…5 (keys)

1 = 0.2 s
2 = 0.5 s
3 = 1.0 s
4 = 2.0 s
5 = 5.0 s

The relay hold interval only starts after other functions have been com-
pleted (delayed).

These pre-programmed settings allow you to configure the system
quickly and easily for standard applications.

CTM prevents an industrial door from being inadvertently opened by vehi-
cles or persons that are only moving or walking past it but do not want to
pass through the industrial door.

F + 5 + 1 =

Aus

S.3 + 1

F + 5 + 2…9

S.3 + 2…9

Optimum inclination angle for crossing traffic function: 30° to 45°

Crossing traffic masking is not possible with the clip!

B + 1 =

On

S.4 + 1

B + 2 =

Off

S.4 + 2

This option must be activated when the mechanical clip is used for set-
ting a wide field. Please refer to 3.1 for information about clip mounting.

The detector will not function correctly if the wrong setting is made.

Industrial door remains closed
to crossing traffic (level 9)

Industrial door opens to crossing traffic
or when an object approaches laterally
(level 1)

Remote
control

Function

Keys

C + 1

Standard, detects all objects

P.1+1

C + 2

Frontal traffic, all objects

P.1+2

C + 3

High-speed industrial door, all objects

P.1+3

C + 4

Detects slow movements, all objects

P.1+4

C + 5

Standard, differentiation between people and
vehicles

P.1+5

C + 6

Frontal traffic, differentiation between people
and vehicles

P.1+6

C + 7

High-speed industrial door, people suppression

P.1+7

C + 8

Detects slow movements, differentiation
between people and vehicles

P.1+8

Note:

The selected enhanced function is only read back and displayed

as such if no parameters were changed. Please refer to the table of
enhanced functions in 4.6 for more details.

Remote
control

Function

Keys

E + 1 + 1

Forwards, movement towards detector

S.2 + 1

E + 1 + 2

Backwards, movement away from detector

S.2 + 2

E + 1 + 3

Forwards and backwards

S.2 + 3

Remote
control

Function

Keys

E + 2 + 1

Standard industrial door, differentiation between
people and vehicles

P.3 + 1

E + 2 + 2

Standard industrial door, people suppression

P.3 + 2

E + 2 + 3

Standard industrial door, vehicle suppression

P.3 + 3

E + 2 + 4

Standard industrial door, people and vehicles,
same output (relay 2)

P.3 + 4

E + 2 + 5

Standard industrial door, people and vehicles,
outputs with direction segregation

P.3 + 5

E + 2 + 6

High-speed industrial door, people suppression
(relay 2)

P.3 + 6

E + 2 + 7

High-speed industrial door, people and vehicles,
same output (relay 2)

P.3 + 7

E + 2 + 8

High-speed industrial door, people and vehicles,
outputs with direction segregation

P.3 + 8

Please also refer to the table of relay parameter settings in point 4.6!

Field without clip

Field with clip

5.16

Slow Motion Detection (SMD) F+3

The slightest (quasi-static) movements are detected as soon as the detec-
tor is activated. The detector only issues the corresponding signal to the
industrial door controller if no more movement is registered during the set
monitoring period. Sensitivity during this monitoring period can be set to
decrease or remain constant.

Summary of Contents for Hercules 2

Page 1: ...den Der Sensor muss auf einer ebenen Fläche fest montiert werden Vibrationen vermeiden Objekte wie Pflanzen Fahnen Ventilatoren usw dürfen nicht in das Detektionsfeld hineinragen Der Sensor darf nicht durch Abdeckungen Schilder verdeckt sein Fluoreszenzlampen in unmittelbarer Nähe des Detektionsfeldes müssen vermieden werden Gerät in der Mitte über dem Tor montieren 1 Bohrschablone an Wand oder De...

Page 2: ...entaste am Sensor x oder y Unterbrechen der Stromzufuhr Mittels Zugangscode mit der Fernbedienung Aufstartphase SMD Slow Motion Detection Kleinste quasi statische Bewegungen werden detektiert sobald das Tor öffnet Es wird erst geschlossen wenn während der eingestellten Über wachungszeit keine Bewegung mehr registriert wird QVA Querverkehrsausblendung Die Querverkehrsausblendung verhindert eine ung...

Page 3: ...Richtungserkennung Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts Stufe 1 vorwärts E 2 Relais parametrierung Stufe 5 R2 vorwärts R1 rückwärts Stufe 5 R2 vorwärts R1 rückwärts Stufe 8 R2 vorwärts R1 rückwärts Stufe 5 R2 vorwärts R1 rückwärts Stufe 1 R2 Fahrzeug R1 Person Stufe 1 R2 Fahrzeug R1 Person Stufe 6 R2 Fahrzeug R1 Stuf...

Page 4: ...wärts und Rückwärts Relaisparametrierung E 2 1 2 3 4 5 6 7 8 Standard Tor Personen Fahrzeug Unterscheidung Standard Tor Personen Unterdrückung Standard Tor Fahrzeug Unterdrückung Standard Tor Personen Fahrzeuge gleicher Ausgang Standard Tor Personen Fahrzeuge Ausgänge richtungsgetrennt Schnelllauftor Personen Unterdrückung Schnelllauftor Personen Fahrzeuge gleicher Ausgang Schnelllauftor Personen ...

Page 5: ...en Taste X oder Y auf dem Sensor Ändern der Funktion Durch Drücken der Taste X Pro Tastendruck erhöht sich der Wert um 1 Funktions Nr Nach Erreichen der letzten Funktion springt das Programm wieder zur ersten Funktion Die grüne LED gibt anschliessend die Nummer der aktivierten Funktion an Ändern der Stufe Durch Drücken der Taste Y Pro Tastendruck erhöht sich der Wert um 1 Stufe Nach Erreichen der ...

Page 6: ...hr geschlossen Stufe 9 Tor öffnet bei Querverkehr oder seitlicher Annäherung Stufe 1 Fernbe dienung Funktion Tasten C 1 Standard erkennt alle Objekte P 1 1 C 2 Verkehr frontal alle Objekte P 1 2 C 3 Schnelllauftor alle Objekte P 1 3 C 4 Erkennt langsame Bewegungen alle Objekte P 1 4 C 5 Standard Personen Fahrzeug Unterscheidung P 1 5 C 6 Verkehr frontal Pers Fahrzeug Unterscheidung P 1 6 C 7 Schne...

Page 7: ... drücken Alle 2 s leuch ten beide LED s kurz auf Gerät ist auf Werkseinstellung zurückgesetzt Funktion Zugangscode ist ausgeschaltet Code gelöscht Neue Initialisierungs und Einlernphase beginnt siehe 4 1 Digitale Filterfunktion Bei speziellen Montagesituationen ist es unter Umständen notwendig die Filterfunktion zu aktivieren Naheliegende Störquellen können zu Fehlauslösungen führen F 6 1 Ein S 7 ...

Page 8: ...ereignung EU EFTA US CA Feldabmessungen bei 30 Neigung Von 2 5 m x 3 m BxT Höhe 2 m Bis 5 m x 7 m BxT Höhe 7 m EU Konformitätserklärung Hiermit erklärt die Bircher Reglomat AG dass sich das Produkt Herkules 2 in Übereinstimmung mit den grundlegenden Anforderungen und den anderen relevanten Vorschriften der Richtlinie 1999 5 EG befindet Die vollständige Konformitätserklärung steht auf unserer Inter...

Page 9: ... mounted on a flat surface Avoid vibrations Objects such as plants flags fans etc must not protrude into the detection area The detector must not be obscured by covers signs Fluorescent lamps should not be placed in the immediate vicinity of the detection area Mount the device in the middle above the industrial door 1 Affix drilling jig to wall or ceiling and drill holes according to values given ...

Page 10: ...etector x or y Interrupting electrical power supply Via access code on remote control Start up phase SMD Slow Motion Detection The slightest quasi static movements are detected as soon as the industrial door opens The industrial door is only closed if no more movement is registered during the set monitoring time CTM Crossing traffic masking Crossing traffic masking prevents an industrial door from...

Page 11: ...backwards Level 5 R2 forwards R1 backwards Level 8 R2 forwards R1 backwards Level 5 R2 forwards R1 backwards Level 1 R2 Vehicle R1 Person Level 1 R2 Vehicle R1 Person Level 6 R2 Vehicle R1 Level 1 R2 Vehicle R1 Person F1 Relay hold interval Level 4 2 s Level 4 2 s Level 4 2 s Level 4 2 s Level 4 2 s Level 4 2 s Level 4 2 s Level 4 2 s F3 SMD Level 1 Off Level 2 Weak Level 1 Off Level 8 Strong Leve...

Page 12: ... 2 1 2 3 4 5 6 7 8 Standard industrial door differentiation between people and vehicles Standard industrial door people suppression Standard industrial door vehicle suppression Standard industrial door people and vehicles same output Standard industrial door people and vehicles outputs with direction segregation High speed industrial door people suppression High speed industrial door people and ve...

Page 13: ...hanging the function Press key X The value increases by 1 for every key press function no Once the last function has been reached the program jumps back to the first function The green LED then indicates the number of the activated function Changing the level Press key Y The value increases by 1 for every key press level Once the last level has been reached the program jumps back to the first leve...

Page 14: ... laterally level 1 Remote control Function Keys C 1 Standard detects all objects P 1 1 C 2 Frontal traffic all objects P 1 2 C 3 High speed industrial door all objects P 1 3 C 4 Detects slow movements all objects P 1 4 C 5 Standard differentiation between people and vehicles P 1 5 C 6 Frontal traffic differentiation between people and vehicles P 1 6 C 7 High speed industrial door people suppressio...

Page 15: ...imultaneously and hold for 8 seconds Both LEDs light up briefly every 2 s Device is reset to factory settings Access code function is switched off Code deleted New initialisation and teach in phase starts see 4 1 Digital filter function In special mounting situations it might be necessary to activate the filter function under certain circumstances Sources of interference located close to the detec...

Page 16: ...m x 3 m WxD height 2 m to 5 m x 7 m WxD height 7 m EU Declaration of Conformity Bircher Reglomat AG herewith declares the product Herkules 2 to be in conformance with the basic requirements and other relevant regulations as contained in the 1999 5 EC Directive The full version of the Declaration of Conformity can be viewed on our internet homepage www bircher reglomat com 1 The warranty and liabil...

Page 17: ...face plane éviter les vibrations Aucun objet tel que plantes drapeaux ventilateurs etc ne doit pénétrer dans le champ de détection Le détecteur ne doit pas être obturer par des recouvrements panneaux Éviter de placer des tubes fluorescents à proximité directe du champ de détection Installer l appareil au milieu et au dessus de la porte d accès 1 Coller le gabarit de perçage au mur plafond et perce...

Page 18: ...mentation électrique au moyen du code d accès avec la télécommande Phase de démarrage SMD Slow Motion Detection détection de mouvements lents Même les moindres mouvements quasi statiques sont détectés dès que la porte s ouvre Elle ne se ferme que lorsqu aucun mouvement n est plus détecté pendant la période de surveillance réglée SCT suppression de la circulation transversale La suppression de circ...

Page 19: ...nt R1 en arrière Degré 8 R2 en avant R1 en arrière Degré 5 R2 en avant R1 en arrière Degré 1 R2 véhicule R1 personne Degré 1 R2 véhicule R1 personne Degré 6 R2 véhicule R1 Degré 1 R2 véhicule R1 personne F1 Temps de maintien du relais Degré 4 2 s Degré 4 2 s Degré 4 2 s Degré 4 2 s Degré 4 2 s Degré 4 2 s Degré 4 2 s Degré 4 2 s F3 SMD Degré 1 inactif Degré 2 faible Degré 1 inactif Degré 8 forte D...

Page 20: ...ais E 2 1 2 3 4 5 6 7 8 Porte standard distinction personnes véhicules Porte standard pas de détection de personnes Porte standard pas de détection de véhicules Porte standard personnes véhicules même sortie Porte standard personnes véhicules sorties différentes pour les deux directions Porte rapide industrielle pas de détection de personnes Porte rapide industrielle personnes véhicules même sorti...

Page 21: ... X ou Y du détecteur Modification de fonction En appuyant sur la touche X Chaque appui sur la touche augmente la valeur de 1 n fonction Une fois que la dernière fonction est atteinte le programme revient à la première fonction La LED verte indique ensuite le numéro de la fonction activée Modification du degré En appuyant sur la touche Y Chaque appui sur la touche augmente la valeur de 1 degré Une ...

Page 22: ... 1 4 C 5 Porte standard distinction personnes véhicules P 1 5 C 6 Circulation frontale distinction pesonnes véhicules P 1 6 C 7 Porte industrielle extra rapide pas de détection de personnes P 1 7 C 8 Détecte les mouvements lents distinction personnes véhicules P 1 8 Remarque La fonction confort sélectionnée n est renvoyée comme telle et affichée que quand aucun paramètre n a été modifié Pour des d...

Page 23: ...commencer à 1 Appuyer simultanément sur les touches de commande X et Y pendant 8 s Les deux LED s allument brièvement toutes les 2 s L appareil est réinitialisé à la configuration d usine La fonction Code d accès est désactivée Code effacé nouvelle phase d initialisation et d apprentissage débute voir 4 1 Fonction de filtre numérique Dans des conditions de montage particulières il peut être nécess...

Page 24: ... les pays EU EFTA US CA Dimensions de champ à inclinaison de 30 de 2 5 m x 3 m l x p hauteur 2 m à 5 m x 7 m l x p hauteur 7 m Déclaration de conformité CE Par la présente la société Bircher Reglomat AG déclare que le produit Herkules 2 est conforme aux exigences fondamentales et aux autres prescriptions applicables de la Directive 1999 5 CE La déclaration de conformité intégrale peut être consult...

Reviews: