2.2.2 Sensor Mode
Mode
Description
LEVEL
Distance from Low Calibration Point to material surface
SPACE
Distance from High Calibration Point to material surface
DISTANCE *
Distance from Sensor Reference Point to material surface (flange face)
2.2.3 Damping Filter: The time constant for the damping filter. The damping filter smooths out the response to a
sudden change in level. This is an exponential filter and the engineering unit is always in seconds.
Value Range: 0 to 1500 s; Default is 10 s
2.2.4 Temperature Units: Selects the engineering units to be displayed with the value representing temperature.
Options: C*, F, R or K
2.5.5 Unit: Sensor measurement units.
2.3 Calibration - We recommend using the Quick Start Wizard to configure the device
2.3.1 Low Calibration Point: Distance from sensor reference point to Low Calibration Point. Units are definited in Units
(2.2.1) and displayed on the LCD.
Value Range: 0 to 100.00 m; Default 100.00 m
Any change to Low Calibration Point will cause the mA setpoints to be updated.
2.3.2 High Calibration Point: Distance from sensor reference point to High Calibration Point. Units are definited in
Units (2.2.1) and displayed on the LCD.
Value Range: 0 to 100.00 m; Default 100.00 m
Any change to Low Calibration Point will cause the mA setpoints to be updated.
When setting the High Calibration Point value, note that echoes are ignored within Near Range.
2.3.3 Sensor Offset: A constant offset (negative or positive) that can be added to sensor value to compensate if the
sensor reference point has shifted. (For example, this could result from adding a thicker gasket or reducing the
standoff/nozzle
height).
Value Range: -100 to 100 m: Default 0.00 m