Installation, Operation and Maintenance Manual
September 2019
MAN720_IMVS2000v2_IOM Rev. 6
Section 6: Configuration Parameters
Configuration Parameters
PARAMETERS OF THE “VIEW/SETUP MODE” MENU
PARAMETER NAME
DESCRIPTION
RANGE
DEFAULT
VALUE
R/W
(1)
AVAILABLE
ON (2) (3)
PST St.
(PST Status)
It is the status of the last “Manual PST” or ”SOVs
Test.” Manual PST or SOV B Test:
“Not Done”: no Manual PST is performed yet.
“Progress”: during the execution of Manual PST
or SOV B Test
“Failed”: if at least one of the following alarms
is generated during the last Manual PST: PSCT,
PSSB, PSFB, PSST, PSFT, PSSP, PSSR, PSLB, PSHB,
PSNM, PSA and PSB.
“Conf_Err”: the command is not performed
due to wrong configuration or “Pos. Req” not
aligned with “Position” or if the command is not
available (“PST En.” or “B. PST Status”) or “PST
Max Time” = 0, CAL or POS or HSP or LSP alarms
active, etc.
Otherwise it is “Passed”.
“Failed” is squelched by “Conf. Err.”
See 8 for details.
“SOV A Test” or “SOV A – SOV B Test”:
“Not Done”: no SOV Test is performed yet.
“Progress”: during the execution of SOV Test
“Failed”: if at least one of the following alarms is
generated during the SOV Test: “PSA” or “PSB”.
“Conf. Err”: the command is not performed
due to wrong configuration, or “Pos. Req” not
aligned with “Position” or CAL or POS or HSP or
LSP alarms are active.
Otherwise it is “Passed”.
“Failed” is squelched by “Conf. Err.”
See 5.1.5 for details.
It is set to “Not Done” after every Calibration,
Baseline Signature, or Baseline PST.
PST St.
(PST Status)
Not Done,
Passed,
Failed,
Progress,
Conf_Err.
R
Local, Serial,
Bus
M. PST Date
(Manual PST Time)
It is the date of the last performed Manual PST
or SOV A Test or SOV A – SOV B Test.
It is set to “01-01-2014” after every Calibration,
Baseline Signature or Baseline PST or Baseline
SOV Test.
01-01-2014
31-12-2099
01-01-
2014
R
Local, Serial,
Bus
M. PST Time
(Manual PST Date)
It is the time of the last performed Manual PST
or SOV A Test or SOV A – SOV B Test.
It is set to “08:00” after every Calibration,
Baseline Signature or Baseline PST.or Baseline
SOV Test
00.00 – 23.59
08.00
R
Local, Serial,
Bus
PST Stored
It indicates the number of the stored PSTs.
It is set to “0” after every Calibration or Baseline
Signature.
It is set to “1” after every Baseline PST successfully
done.
0-50
0
R
Local, Serial,
Bus
PST ID
It indicates the PST whose data are shown in the
“PST Info.”
The PST ID 1 is dedicated to the Baseline PST.
The last PST (not the Baseline PST) has the ”PST
ID” = 2 and the oldest PST has the “PST ID” = “PST
Stored.”
In case of “SOV A Test” or “SOV A – SOV B Test,"
PST ID 1 is dedicated to the Baseline SOV Test. The
last SOV Test has the “PST ID” = “2” and the oldest
SOV Test has the “PST ID” = “PST Stored.”
1-50
0
R/W
Local, Serial,
Bus
49