Installation, Operation and Maintenance Manual
September 2019
MAN720_IMVS2000v2_IOM Rev. 6
Section 6: Configuration Parameters
Configuration Parameters
PARAMETERS OF THE “VIEW/SETUP MODE” MENU
PARAMETER NAME
DESCRIPTION
RANGE
DEFAULT
VALUE
R/W
(1)
AVAILABLE
ON (2) (3)
B. Cl. B. T.
(Baseline Closing
Break Time)
It is the time measured during the Baseline
Signature (Closing FST) that occurred for going
from the Starting Open position to the 100% -
“Op. Break Pos.” See Section 5.1.6 for details.
0–1000.0 sec
0 sec
R
Local, Serial,
Bus
M. Cl. B. T.
(Maintenance Closing
Break Time)
It is the time measured during the last required
Closing FST that occurred going from the
Starting Open position to the 100% - “Op. Break
Pos”. See 5.1.6 for details. It is not updated in
case of External Source FST and Digital Input
FST with “M. FST Alr En.” = “No.”
See Section 5.2.8 for details.
0–1000.0 sec
0 sec
R
Local, Serial,
Bus
B. Cl. T. T.
(Baseline Closing
Travel Time)
It is the time measured during the Baseline
Signature (Closing FST) that occurred for going
from the 100% - “Op. Break Pos” to the “Cl.
Break Pos.” See Section 5.1.6 for details.
0–1000.0 sec
0 sec
R
Local, Serial,
Bus
M. Cl. T. T.
(Maintenance Closing
Travel Time)
It is the time measured during the last required
Closing FST that occurred for going from the
100% - “Op. Break Pos” to the “Cl.Break Pos.”.
See Section 5.1.6 for details.
It is not updated in case of External Source FST
and Digital Input FST with “M. FST Alr En.” =
“No”. See Section 5.2.8 for details.
0–1000.0 sec
0 sec
R
Local, Serial,
Bus
B. Cl. B. P.
(Baseline Closing
Break Pressure)
It is the pressure measured during the Baseline
Signature (Closing FST) when the position
reaches 100% - “Op. Break Pos”. See Section
5.1.6 for details. If “Act. Mode” ≠ “Single”, this
pressure value is made by the absolute value of
the difference between Pressure 1 and 2.
0 – 400 bar
(0 – 5800 psi)
0 bar
R
Local, Serial,
Bus
M. Cl. B. P.
(Maintenance Closing
Break Pressure)
It is the pressure measured during last required
(managed by the IMVS2000v2) Closing FST
when the position reaches 100% - “Op. Break
Pos”. See Section 5.1.6 for details.
If “Act. Mode” ≠ “Single”, this pressure value is
made by the absolute value of the difference
between Pressure 1 and 2.
It is not updated in case of External Source FST
and Digital Input FST with “M. FST Alr En.” =
“No.” See Section 5.2.8 for details.
0 – 400 bar
(0 – 5800 psi)
0 bar
R
Local, Serial,
Bus
Base. PST Cmd
(Baseline PST
Command)
It is the command for performing the “Baseline
PST” or “Baseline SOV Test.”
The “Baseline PST” can be performed only if
a Baseline Signature is already successfully
performed (“Base S. Status” = “Passed”), if “PST
En.” = “Yes” and if the CAL alarm is not active.
See Section 5.1.5 for details.
The “Baseline SOV Test” can be performed only
if a “Baseline Signature is already successfully
performed (“Base S. Status” = “Passed”), if “PST
En.” = “No”, if “PST Pos %” = “0.0%”, if “PST Pr.
%” = 0% and if “PST Time %” = “0%”.
See Section 5.1.6 for details.
The ”Baseline PST” / “Baseline SOV Test” deletes
all the previous PSTs / SOVs Tests stored.
Start
C
Local, Serial,
Bus
47