UPSI-IP-3 Series
Revision 1-0
26
72
96
120
144
168
192
216
0
10
20
30
40
50
60
P
OU
T
[W]
I
OUT
[A]
4s
10s
12s
10s
4s
4s
4s
8s
2s
P
OUT Nominal
58
E
P
out
[
W
]
Time
[
t
]
Before second 0
no load was taken.
After second 58
the device keeps
running, output
remains free.
Example 1 (UPSI-2406DP1 / UPSI-2406DP2)
E = 72 W · 4 sec + 120 W · 10 sec + 168 W · 12 sec + 192 W · 10 sec + 144 W · 4 sec + 192 W · 4 sec + 96 W · 4sec + 0 W · 8 sec + 120 W · 2 sec = 7392 Ws = 7.392 kJ
UPS output keeps unlocked after second 58 because the output energy does not exceed 8.35 kJ.
72
96
120
144
168
192
216
0
10
20
30
40
50
60
P
OU
T
[W]
I
OUT
[A]
4s
24s
4s
8s
5s
P
OUT Nominal
8s
2s
3s
58
E
P
out
[
W
]
Time
[
t
]
Before second 0
no load was taken.
After second 58
output is disconnected.
Example 2 (UPSI-2406DP1 / UPSI-2406DP2)
E = 0 W · 4 sec + 192 W · 24 sec + 96 W · 4 sec + 168 W · 8 sec + 192 W · 8 sec + 0 W ·2 sec + 120 W · 5 sec + 0 W · 3 sec = 8472 Ws = 8.472 kJ
UPS output is disconnected after 58 seconds because the output energy exceeds 8.35 kJ.
.