EMISSION ACCORDING TO EN 62040-2 Uninterruptible Power Supply Systems –
Part 2: Part 2: Electromagnetic compatibility requirements (EMC)
Basic standard
Fulfilled requirements according to EN 62040-2
Conducted emission from the power port
CISPR 22
Frequency range
Comment
150 kHz–30 MHz
Class A
Electric field radiated emission
CISPR 22
Frequency range
Comment
30 MHz–1 GHz
Class A*
Electric field radiated emission
CISPR 22
Frequency range
Comment
1 GHz–6 GHz
Class A
*To improve the emitted interference, Bicker Elektronik recommends installing the "Würth 74272722" ferrite (not in scope of delivery) in the DC
output cable of the UPS directly after the housing outlet (2 turns).
HARMONIC CURRENTS ACCORDING TO EN 62040-2 Uninterruptible Power Supply
Systems – Part 2: Part 2: Electromagnetic compatibility requirements (EMC)
Basic standard
Fulfilled requirements according to EN 62040-2
Measurement of harmonic currents
EN 61000-3-2
Comment
Passed