INPUT DATA
Input voltage
100…240 V AC nominal (±10 %), active PFC
Input frequency
50…60 Hz nominal (±10 %)
Inrush current
<100 A (bei I
IN
= 220 V AC)
Current consumption
I
IN NOM
(I
OUT
= 6 A, I
CHARGE
= 0)
I
IN MAX
(I
OUT
= 6 A, I
CHARGE
= max)
I
IN DYN
(I
OUT
= I
DYN.BOOST
, I
CHARGE
= 0)*
I
IN NO-LOAD
(I
OUT
= 0, I
CHARGE
= 0)
I
IN CHARGE
(I
OUT
= 0, I
CHARGE
= max)
At 220 V AC
IN
0.74 A
0.9 A
1.0 A
<100 mA
0.3 A
At 100 V AC
IN
1.58 A
2.1 A
2.2 A
<100 mA
0.65 A
Power consumption
P
IN NOM
(I
OUT
= 6 A, I
CHARGE
= 0)
P
IN MAX
(I
OUT
= 6 A, I
CHARGE
= max)
P
IN DYN
(I
OUT
= I
DYN.BOOST
, I
CHARGE
= 0)*
P
IN NO-LOAD
(I
OUT
= 0, I
CHARGE
= 0)
P
IN CHARGE
(I
OUT
= 0, I
CHARGE
= max)
At 220 V AC
IN
155 W
190…196 W
220 W
<2 W
62…63 W
At 100 V AC
IN
156 W
205…210 W
221 W
<2 W
63…64 W
Efficiency
App. 90.5…91.5 % at I
IN NOM
(I
OUT
= 6 A, I
CHARGE
= 0)
App. 87.0…88.5 % at I
IN CHARGE
(I
OUT
= 0, I
CHARGE
= max)
Internal input fuse
2x 5 A / 250 V AC
Switch-on time
<5 sec
Switch-on time battery start (BS)
<5 sec
Backup fuse
B16 230 V AC
20 A / 120 V AC, IEC/EN Listed breaker, Type B
D Technical Data
D1 General Technical Data
All specifications at the housing inlet/housing outlet, without line losses, at ambient temperature of 25°C
*Max. 58 sec., depending on output power (see also „F11 Dynamic Powerboost“)