ENGLISH

INSTALLATION MANUAL

2) GENERAL OUTLINE

ALCOR N mod. control unit has been designed to be applied on swing gates. It 
can control one or two operators.

3) TECHNICAL DATA

Power supply:  ...................................................................................... 220-230V 50/60Hz(*)
Mains insulation/very low voltage:  .....................................................> 4M

, 500V

Working temperature: .......................................................................................... -10 / +55°C

Dielectric strength:…. ....................................mains/low voltage 3750V~ for 1 minut

Maximum motor power ................................................................................. 1 motor 300W

...............................................................................................................2 motors 300W + 300W

Supply to accessories:  ........................................................24V~, (0.2A max absorption)

Incorporated Rolling-Code radio receiver:  .............................Frequency 433.92MHz

Coding:  ...................................................................Rolling-Code Algorithm to be cloned

No. combinations: ...................................................................................................... 4 milliard

Antenna impedance: .....................................................................................  50Ohm (Rg58)

Max no. radio transmitters to be memorised: ................................................................63

Dimensions:  .............................................................................................................see figure 1
(* other voltages available on request)

4) TERMINAL BOARD CONNECTIONS (Fig.2)

For the wiring diagram and the cable section, make reference to the operator’s 

manual.

WARNING! For connection to the mains, use a multipolar cable with a 

minimum of 3x1.5mm

2

 cross section and complying with the previously 

mentioned regulations. For example, if the cable is out side (in the open), it 

has to be at least equal to H07RN-F, but if it is on the inside (or outside  but 

placed in a  plastic cable cannel) it has to be or at least egual to H05VV-F 

with section 3x1.5mm

2

.

1-2 Power  supply  220-230V 50/60Hz (Neutral wire to terminal 1).

3-4-5  M1 motor connection (terminal 4 common wire, terminals 3-5 motor and 

capacitor operation).

1-4 Blinker connection 220-230V

6-7-8  M2r motor connection (terminal 7 common wire, terminals 6-8 motor and 

capacitor operation).

1-7 Electric lock connection 220-230V mod. EBP.

9-10  Input for START Button (N.O.).

9-11  Input for STOP Button (N.C.). If not used, leave bridged. 

9-12  Input for Photocell (N.C.). If not used, leave bridged.

9-13  Input with function selectable from DSW9:

    with DSW9 OFF, Input for Opening Limit Switch (N.C.). If not used, leave 

bridged.   

 

 

with DSW9 ON Input for OPEN Button (N.O.).*

9-14  Input with function selectable from DSW9 and DSW10:

    with DSW9 OFF, Input for Closing Limit Switch (N.C.). If not used, leave 

bridged.  

 

 

with DSW9 ON and DSW10 OFF, Input for CLOSE Button (N.O.).* 

    with DSW9 ON and DSW10 ON, Input for PEDESTRIAN Button (N.O.). The 

pedestrian command is active from gate fully closed; if the gate is not 

closed, the PEDESTRIAN button carries out the START functions.* 

15-16  Output 24V for accessory power supply 200mA MAX.

17-18 Output for second radio channel, N.O. contact (24V / 1A max.). If an external 

receiver is used, it must be a double-channel receiver.

 

 

A dry N.O. contact must be electrically connected to the terminals.

19-20  Input for receiver antenna (20 Braid, 19 Signal).

*With operation without limit switches, the motors remain active for the working 

time set.
RX  

Connector for the external receiver board.

5) LED (Fig.3)        

The ALCOR N control units are provided with a series of self-diagnosis LEDs 
which control all the functions.

POWER:  Led for power supply on.

OP:     Led for Signal indication of Motors active on Opening / Led for Radio 

Programming.

CL:   Led for Signal indication of Motors active on Closing.

START:  It comes on with the START command.

STOP: goes off when a STOP command is given.

PHOT: photocell - goes off when the photocells are not aligned or in the presence 

of obstacles.

SWO:    Led for signal indication of input 13 status: 

 

 

 

led on= input closed, led off= input open.

SWC:    Led for signal indication of input 14 status:
 

 

 

led on= input closed, led off= input open.

6) DIP-SWITCH SELECTION (Fig.3)
DIP1) TCA [ON] - Automatic closing time TCA.

ON:  Activates automatic closing

OFF:  Excludes automatic closing
DIP2) FCH [OFF] - Photocells.
ON:  Photocells are only active in the closing phase. If the photocells are ob-

structed during closing, the gate reverses its movement and carries out 
an opening manoeuvre.

OFF:  Photocells are active both in the closing and opening phase. If the photo-

cells are obstructed, the gate stops. When the photocells are cleared, the 

gate resumes it opening manoeuvre.

DIP3) BLI -[OFF] Blocks impulses.
ON:  START commands are not accepted during the opening phase.
OFF:  START commands are accepted during the opening phase.
DIP4) 3P/4P -[OFF] 3 Steps/4 Steps 

ON:  Enables 3-step logic. A start impulse has the following effects: 

 

door closed:..............................................................................opens

 

on opening:.................................stops and enters TCA if configured

 

door open:................................................................................closes

 

on closing:................................................................................opens

 

after stopping:...........................................................................opens

OFF:  Enables 4-step logic.  A start impulse has the following effects:

 

door closed:..............................................................................opens

 

on opening:.................................stops and enters TCA if configured

 

door open:................................................................................closes

 

on closing:................................stops and does not enter TCA (stop)

 

after stopping:...........................................................................opens

DIP5) CODE FIX [OFF] – Fixed code.
ON:  Activates incorporated receiver in fixed code mode.
OFF:  Activates incorporated receiver in rolling-code mode.
DIP6) RADIO LEARN [OFF] - Radio transmitter programming
ON:  This enables transmitter storage via radio:

 

1 – First press the hidden key (P1) and then the normal key (T1, T2, T3 or 

T4) of a transmitter already  memorised in standard mode by means of 

the radio menu.

 

2 – Within 10s press the hidden key (P1) and the normal key (T1, T2, T3 or 

T4) of a transmitter to be memorised.

 

The receiver exits the programming mode after 10s, other new transmitters 

can be entered before the end of this time. 

 

This mode does not require access to the control panel.

OFF:  This disables transmitter storage via radio. The transmitters can only be 

memorised by pressing the SW1 and SW2 keys (see paragraph 10).

DIP7) STOP MAINTENANCE [OFF]

ON:  If motors stay idle in fully closed position for more than one hour, they 

are switched on in the direction of the stop for approx. 3 seconds. This 

operation is performed every hour. 

 

N.B.: This function has the purpose of compensating any oil volume decre-

ase in the hydraulic motors, due to a temperature drop during prolonged 

pauses, for instance at night, or to internal leaks. 

 

IMPORTANT - When no adequate mechanical backstops are installed, do 

not use this function. It is also to be  absolutely avoided in the automation 

of sliding gates.

OFF:  Excludes the said function.

DIP8) Ram blow on opening [OFF]

ON:  It pushes for approx. 2 seconds in closing direction before opening. This 

allows the electric lock to be released more easily (not affected by limit 

switches).

OFF:  Excludes the ram blow in closing.

 

IMPORTANT - When no adequate mechanical backstops are installed, do 

not use this function. It is also to be  absolutely avoided in the automation 

of sliding gates.

DIP 9) Function Selection for inputs 13-14 Limit Switches / Buttons 

ON:   Inputs 13 and 14 are set as Control button inputs. Input 13 for OPEN button, 

input 14 according to DSW 10 configuration. With this configuration, the 

motors remain active for the working time set.

OFF:  Inputs 13 and 14 are set as Opening and Closing limit switch inputs, 

respectively.

DIP 10) Function Selection for control button inputs 13-14*  

N.B. Only with DSW 9 ON. With DSW 9 OFF, the DSW 10 position has no effect.

OFF:  Input 14 configured as CLOSE input.

ON:  Input 14 configured as PEDESTRIAN input.

*If, when the board is activated, the closing limit switch is neither enabled nor 

operating, at the time of the first manoeuvre neither the ram blow nor the pe-

destrian opening are carried out. 
7) TRIMMER ADJUSTMENT 
(Fig.3)
TCA (Dip1 ON).
It is used to set the automatic closing time, after which the gate closes automa-
tically (adjustable from 0 to 120 sec.).
TW
It is used to set the motor working time, after which the motor stop (adjustable 
from 1 to 90 sec.). When using electrical limit switches, increase the motor stopping 

ALCOR N- 

9

D811509_05

Summary of Contents for ALCOR N

Page 1: ...Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente las Advertencias en el interior Atenção Ler atentamente as Instruções que se encontram no interior D811509_05 22 05 15 ALCOR N 9 10...

Page 2: ...OP PHOT SWO N C OPEN N O SWO N C CLOSE PED N O 24V II RC 0V NO N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ANTENNA ANTENNE ANTENNA ANTENA ANTENNE M2r M1 L NC NC ALCOR N Fig 1 237 207 195 165 100 5 2 ALCOR N D811509_05 ...

Page 3: ...ITALIANO ENGLISH FRANÇAIS DEUTSCH ESPAÑOL PORTUGUÊS Fig 4 Fig 5 Fig 6 Fig 6A SWC N C ALCOR N ALCOR N ALCOR N ME SS ALCOR N SS SPL ALCOR N 3 D811509_05 ...

Page 4: ...acts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos Contatti Contacts Contacts Kontakte Contactos Contatos UNIFLAT UNIFLAT UNIFLAT UNIMITTO UNITRC UNITRC UNIDA ALCOR N UNIFLAT 4 ALCOR N D811509_05 ...

Page 5: ...ermanenteunaetichettarelativaalfunzionamentodellosblocco manuale dell automazione e apporla vicino all organo di manovra Assicurarsi che durante la manovra siano evitati o protetti i rischi meccanici ed inparticolarel impatto loschiacciamento ilconvogliamento ilcesoiamentotra parte guidata e parti circostanti Dopo aver eseguito l installazione assicurarsi che il settaggio dell automazione motore s...

Page 6: ... Se si occupano le fotocellule durante la chiusura il cancello inverte il movimento ed esegue un apertura OFF Fotocellule attive in chiusura ed apertura Se si occupano le fotocellule il cancello si ferma Quando si liberano le fotocellule il cancello riparte in apertura DIP3 BLI OFF Blocca impulsi ON Durante la fase di apertura non accetta i comandi di START OFF Durante la fase di apertura accetta ...

Page 7: ...CENTRALINA Per cancellare totalmente la memoria della centralina premere contemporanea mente per 10 secondi i pulsanti SW1 e SW2 nella centralina il led OP lampeggia La corretta cancellazione della memoria sarà segnalata dal Led OP acceso fisso Per uscire dal modo di memorizzazione attendere fino al completo spegnimento del led 11 CONFIGURAZIONE RICEVITORE Ilricevitoreabordoditipoclonabileuniscele...

Page 8: ...g light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that during operation mechanical risks are avoided or relevant protective measures taken and more specifically that nothing can be banged crushed caughtorcutbetweenthepartbei...

Page 9: ... are ob structed during closing the gate reverses its movement and carries out an opening manoeuvre OFF Photocells are active both in the closing and opening phase If the photo cells are obstructed the gate stops When the photocells are cleared the gate resumes it opening manoeuvre DIP3 BLI OFF Blocks impulses ON START commands are not accepted during the opening phase OFF START commands are accep...

Page 10: ... press for 10 seconds the SW1 and SW2 buttons on the control unit OP LED blinking Correct memory cancellation will be indicated by the OP LED staying on perma nently To exit the storage mode wait until the LED is switched off completely 11 RECEIVER CONFIGURATION Theon boardreceivercombinescharacteristicsofutmostsafetyincopyingvaria ble code rolling code coding with the convenience of carrying out ...

Page 11: ...ions d entretien ou les réparations Le Fabricant décline toute responsabilité quant à la sécurité et au bon fonctionnement de l automatisation en cas d utilisation de composants d autres Fabricants Ne modifier d aucune façon les composants de l automatisation sans l autorisa tion expresse du Fabricant Informer l utilisateur de l installation sur les risques résiduels éventuels sur les systèmes de ...

Page 12: ...tive la fermeture automatique OFF Exclut la fermeture automatique DIP2 FCH OFF Cellules photoélectriques ON Cellules photoélectriques activées seulement en fermeture Si les cellules photoélectriques sont occupées pendant la fermeture le portail invertit le mouvement et s ouvre OFF Cellules photoélectriques activées en fermeture et en ouverture Si les cellules photoélectriques sont occupées le port...

Page 13: ...T DE LA MÉMOIRE DE L UNITÉ DE COMMANDE Pour effacer totalement la mémoire de la centrale appuyer en même temps pendant 10 secondes sur les touches SW1 et SW2 de la centrale la Led OP cli gnote L effacement effectif de la mémoire sera signalé par la Led OP allumée en permanence Pour sortir du mode de mémorisation attendre l extinction complète de la led 11 CONFIGURATION DU RECEPTEUR Le récepteur mo...

Page 14: ...e bei allen Wartungs und Reparaturarbeiten ausschließlich Originaler satzteile Die Firma haftet nicht für die Sicherheit und den ordnungsgemäßen Betrieb der Automatik falls Komponenten von anderen Herstellern verwendet werden Nehmen Sie keine Änderungen an den Komponenten der Automatik vor die von der Firma nicht ausdrücklich genehmigt werden Unterweisen Sie die Benutzer der Anlage hinsichtlich de...

Page 15: ...ßvorgangsverdunkeltwerden kehrtdasTordieBewegungsrichtung um und öffnet sich OFF Lichtschranke bei Schließung und Öffnung aktiv Wenn die Fotozellen ver dunkelt werden bleibt das Tor stehen Sobald die Fotozellen wieder frei sind startet das Tor einen Öffnungsvorgang DIP3 BLI OFF Impulsblockierung ON WährendderÖffnungsphasewerdenkeineSTART Befehleangenommen OFF Während der Öffnungsphase werden START...

Page 16: ...10 1 LÖSCHEN STEUERUNGSSPEICHER UmdenSpeicherderSteuerungvollständigzulöschen drückenSiebittegleichzei tigfür10SekundendieKnöpfeSW1undSW2inderSteuerung dieLedOPblinkt WennderSpeicherkorrektgelöschtwurde leuchtetdieLedOPdurchgehendauf Um den Speichermodus zu verlassen warten Sie bis die Led ganz erloschenist 11 KONFIGURIERUNG EMPFÄNGER Der integrierte klonierbare Empfänger vereint den Vorzug extrem...

Page 17: ...iento y reparación La Empresa no se responsabiliza de la seguridad y el buen funcionamiento de la automatización en caso que se utilicen componentes de otros fabricantes No realizar ninguna modificación a los componentes de la automatización si no se cuenta con autorización expresa por parte de la Empresa Instruir al usuario de la instalación sobre los eventuales riesgos residuales los sistemas de...

Page 18: ... fotocélulas durante la fase de cierre la cancela invierte el movimiento y ejecuta una maniobra de apertura OFF Fotocélulas en función en fase de cierre y apertura Si se ocupan las fo tocélulas lacancelasedetiene Cuandoseliberanlasfotocélulas lacancela vuele a ponerse en marcha con una maniobra de apertura DIP3 BLI OFF Bloquea impulsos ON Durante la fase de apertura no acepta órdenes de START OFF ...

Page 19: ...los transmisores 10 1 CANCELACION DE LA MEMORIA DE LA CENTRAL DE MANDOS Para cancelar totalmente la memoria de la central de mandos es preciso pulsar al mismo tiempo y durante 10 segundos los botones SW1 y SW2 de la central el led OP parpadea La correcta cancelación de la memoria se indicará por medio del led OP que se encenderá de manera fija Para salir de la modalidad de memorización es preciso ...

Page 20: ...esbloqueio manual do automatismo e colocá la perto do órgão de manobra Acertar se de que durante a manobra sejam evitados ou protegidos os riscos mecânicos e em especial o esmagamento o arrastamento a tesourada entre a parte guiada e as partes circunstantes Depoisdeterefectuadoainstalação acertar sedequeoajustedoautomatismo esteja correctamente definido e que os sistemas de protecção e de desbloqu...

Page 21: ...ático DIP2 FCH OFF Fotocélulas ON Fotocélulas activas unicamente no fecho Se ocupam se as fotocélulas durante o fecho o portão inverte o movimento e executa uma abertura OFF Fotocélulas activas no fecho e na abertura Se ocupam se as fotocélulas o portão fecha se Quando se libertam as fotocélulas o portão reparte em abertura DIP3 BLI OFF Blocca impulsi ON Durante la fase di apertura non accetta i c...

Page 22: ...po por 10 segundos os botões SW1 e SW2 na central o Led OP pisca para cancelar completamente a memória O correcto cancelamento da memória será sinalizado pelo Led OP aceso em modo fixo Para sair do modo de armazenamento aguardar que o led se apague completamente 11 CONFIGURAÇÃO DO RECEPTOR O receptor a bordo de tipo clonável reúne as características de extrema segu rança da cópia da codificação co...

Page 23: ......

Page 24: ...n 12 BENELUX BFT BENELUX SA 1400 Nivelles www bftbenelux be POLAND BFT POLSKA SP Z O O 05 091 ZąBKI www bft pl CROATIA BFT ADRIA D O O 51218 Drazice Rijeka www bft hr PORTUGAL BFT SA COMERCIO DE AUTOMATISMOS E MATERIAL DE SEGURANCIA 3020 305 Coimbra www bftportugal com CZECH REPUBLIC BFT CZ S R O Praha www bft it TURKEY BFT OTOMATIK KAPI SISTEMELERI SANAY VE Istanbul www bftotomasyon com tr RUSSIA...