15
Table 2. Inverter Log Reason Codes
Alarm Log
The alarm log is in menu 9, submenu 2. Move through the menu structure by pressing the “Menu” button and
pressing
t
to move down to menu 9. Press
¿
, and press
t
to move down to submenu 2. The display shows the
most recent entry in the alarm log.
The log stores up to 16 entries, in chronological order. You can use the
s
and
t
buttons to scroll up and down
through the log entries. Each entry shows the alarm code, the alarm date and time (in 24-hour time), and the
duration (in hours and minutes.)
A typical entry might look like this:
In this example, the sixth most-recent alarm (9 2 6) is being displayed. “
A
” means the Axxium Pro system
sounded alarm A (Low Battery). If the alarm is still active, an asterisk (
*
) is displayed beside the “
A
.”
“
02/05
” is the date the alarm occurred: February 5. “
1751
” means the alarm sounded at 5:51 p.m. And
“
04:35
” means the alarm was active for 4 hours and 35 minutes.
Section 500 contains three tables explaining the alarm codes.
404 Menu Map
Figure 7 is an illustration of how to access all Axxium Pro system parameters. The menu structure has 12
primary-level menus, named Password (1) through Parameters (12). Under each primary menu are secondary
items, each numbered by its location under the primary menu. Use the various buttons as shown in the map to
navigate to the desired parameter. If you need to change the value of a parameter, you must begin by entering
the correct password value first. Parameter values can be observed, but most can not be changed, even though
you have entered the correct user password.
Reason
Code
Meaning
Explanation
1
Line Was Lost
Input voltage was lost.
2
Battery Test
Battery test initiated inverter operation.
3
Manual
Operator initiated inverter operation.
4
Open Cell
Battery failure caused by open cell.
5
Weak Battery
Battery failure caused by load test.
12
11
10
9
8
7
6
Incompatible Module
Insufficient Modules
Insufficient Batteries
Precharge Failure
Excessive Transfers
Module Failure
Phase Error
Wrong type of power module for intended system configuration.
Too few power modules; decrease load or add power modules.
Too few battery modules; decrease load or add battery modules.
Internal error – phone Best Power Worldwide Service or your nearest Best Power office.
Internal error – phone Best Power Worldwide Service or your nearest Best Power office.
Internal error – phone Best Power Worldwide Service or your nearest Best Power office.
Internal error – phone Best Power Worldwide Service or your nearest Best Power office.
9 2 6
#0
Alarm Log 1
A 02/05 17:51 04:35
Slot
Top
ESC