37
1107 Location Requirements
Install the Axxium Pro UPS as close as possible to the equipment or the load distribution panel it will protect. If
this distance is more than 25 feet (7.6 m), transient noise can reappear in the electrical distribution system.
If additional Axxium Pro system batteries are in a separate cabinet, the battery cabinet should be located as close
as possible to the Axxium Pro UPS. If the batteries will be further from the unit than the standard cables allow,
contact your nearest Best Power office for assistance.
1108 Moving the Axxium Pro UPS and Battery Cabinets
Refer to Section 1200 for information about initial equipment unpacking.
The Axxium Pro UPS and the battery cabinet are very heavy with battery modules and power modules installed.
Before moving the cabinets, remove the battery modules and power modules and move these modules separately
from the cabinets.
The smaller (3-slot and 6-slot) cabinets may be ordered with a caster cart, to enable moving the cabinet.
Section 1105 describes how to set the four foot pads on this cart to keep the cabinet from rolling when properly
positioned.
The larger (9-slot and 12-slot) cabinets have casters built into the cabinet base. Use the procedure below to raise
the cabinet before rolling it on its casters. For 12-slot cabinets that do not have output isolation, refer to Section
1106, for details about mounting stabilizer brackets before rolling the cabinet into place.
1. Ensure that the cabinet contains no battery modules and power modules.
2. Locate the four plastic caps covering the caster bolts. They are at the corners of the cabinet base.
3. Pry the caps out of the bolt access holes.
4. Use a 1/2-in. hex-style socket wrench to turn each of the four bolts clockwise. Doing so lowers the casters to
allow the cabinet to roll on the casters.
5. After rolling the cabinet to its intended position, turn the four bolts counter-clockwise. When fully lowered,
the UPS weight is removed from the casters and the base should rest in a level position on the floor.
NOTE: If the floor is uneven and the cabinet is tilted or unstable, you may need to place a thin steel plate
under a corner to make the cabinet stand vertical. Do not use caster bolts to level the cabinet.
After properly positioning and leveling the cabinet, insert battery modules and power modules into the rack as
described in Section 300.