Environment
Humidity
0 - 80% (non condensing)
Meter Operating
10°C to 40°C nominal
Temperature
Storage Temperature
0°C to 50°C nominal
Altitude
2000m above sea level
maximum
Aux Supply
100 – 240V~ 50/60 Hz
< 20W
nominal Power
Consumption
Current
20mA
Electrical Metering
Nominal Full Scale
346V~LN/600V~LL
Voltage
Voltage Category III
Withstand Voltage
1000V~ LN & LL
Input Impedance
> 2M
Ω
Metering Frequency
50/60 Hz nominal
Pickup Voltage
0V
Voltage Accuracy
Better than 1%
CT Type
Split Core - Measurement
Category III compliant
ONLY to UL2808, 333 mV
output per channel
nominal,Max 1V
CT Operating
-40C to +55C
Temperature
CT Max Primary Voltage
600V~
CT Nominal Current
According to available CT’s
Metering Range
30-300 Amps as standard
in stock on ECOS. 500 to
6000 amps available on
request.
Withstand Current
6 x Nominal CT Current
Pickup Current
0A
Accuracy
+/-1% as per IEC60044-1,
Table 11
[ S E C T I O N 7 ]
T E C H N I C A L S P E C I F I C AT I O N S
[ E N S C O P E H Y B R I D M A N U A L ]
52