Important Safety Information
Warning
Read all documentation prior to service or
installation
Important: Must be certified to UL2808, XOBA
for field installation.
Only to be installed in a ambient temperatures
between -40C and +55C. Maximum altitude 2000
meters.
1.
The recommended current transformer
types are intended for field installation
within distribution and control equipment
to measure electrical current.
2.
Always disconnect the circuit from the
power distribution system before service
or installation.
3.
Do not install the current transformers in
an area blocking ventilation or in an area
of breaker arc venting.
4.
These current transformers are not suit
able for Class II wiring methods or
connecting to Class II equipment.
5.
Do not allow the current transformer or
cables to come into direct contact with
live terminals or buss that exceeds
voltages of 600V~.
6.
The CT may not be installed in equipment
where they exceed 75% of the wiring
space of any cross-sectional area within
the equipment.
Installation Instructions for
Current Transformers
Important Safety
Information
Caution, risk of
electric shock
[ E N S C O P E H Y B R I D M A N U A L ]
16