DALIK
- Gateways
Programming manual
v1.4.3
www.besknx.c
z
6
3.2
Individual address assigment
The DALIK Gateway has a programming button for the KNX individual address assignment which is located on the front of
the device.
A red led near the programming button lights up when it is pressed manually or if the device is set remotely to programming
mode state.
The led is automatically turned off if the ETS has assigned an individual address correctly or if the programming button is
pressed again manually.
To carry out an on-line configuration of the gateway a previous individual address assignment is required. If the
DALIK gateway has a different individual address, has no address assigned or the ETS cannot connect to it due
to any other reason, the plug-in application will show a failure and it will not change to on-line mode.
3.3
Communication objects tables
To show the DALIK gateway communication objects in the ETS project it is necessary to add to the gateway memory a
number of DALI lights or groups.
The communication objects associated to each DALI individual ballast or DALI group will be shown or hidden according to
the configuration that is done with the parameters plug-in. This DALI configuration can be done “on-line” or “off-line”.
3.3.1
DALI ligth objects
These are the objects that are available for each DALI individual light (standard ballast and emergency):
Objeto
Nombre | Función
Longitud
DPT
Flags
C
R
W
T
U
0
DALI ballast X | On/off
1 bit
1.001
●
●
●
1
DALI ballast X | On/off status
1 bit
1.001
●
●
●
2
DALI ballast X | Value
1 byte
5.001
●
●
●
3
DALI ballast X | Value status
1 byte
5.001
●
●
●
4
DALI ballast X | Dimming
4 bits
3.007
●
●
●
5
DALI ballast X | Lamp failure
1 bit
1.001
●
●
●
1129
DALI ballast X | DALI individual scene
1 byte
18.001
●
●
●