3.6.3
Address change
By this function, the programmer can edit the address of any DALI device (value from 0 to 63) and click on “apply” to send
the new value in order to change it. The new DALI Address will be assigned to the previous addressed DALI ballast.
In the example picture, by pressing apply the current address of the DALI device 0 will be changed to 33. Remember that
any on-line function of the DALIK gateway requires a previous individual address assignment.
If the address already exists in the DALI project (the current DALI tree) it cannot be changed.
By using this function, the DALI address of the selected ballast will change. The plug-in shows an error if the
address is already in use in the project but it could also exist in the DALI installation if the nodes were added
manually, so in this case two DALI ballasts will take the same individual address.
3.6.4
Localization and check tools
3.6.4.1
Individual light or group
The DALIK application gives the on-line possibility of testing functionalities for individual DALI light or DALI groups localization
and check.
Select the DALI light or group to be test in the project tree on the left and use the “maximum level” or “off” buttons.
On: To dim the DALI ballast to 100% brightness.
Off: To dim the DALI ballast to 0% brightness.
Blink: Make the DALI ballast start blinking. Do click again to stop.