For better use, remember that:

-  a periodic external cleaning with soapy water not only improves its aesthetic 

aspect but also preserves panelling from corrosion, extending its life cycle;

-  if the wall-mounted boiler is enclosed in pendant furniture, leave at least 5 cm 

for ventilation and maintenance;

installation of an ambient thermostat will favour a greater comfort, a more rational 

use of the heat and energy saving; the boiler can also be connected to a program

-

ming clock in order to manage ignition and switching off during the day or week.

2A IGNITION

First ignition must be carried out by personnel from the Technical Assistance 

Service. At the same time, if it is necessary to put the appliance in service again, 

carefully follow the described operations.

To start-up the boiler it is necessary to carry out the following operations:

-  power the boiler

-  open the gas tap present in the system to allow fuel flow 

-  turn the mode selector to the desired position:

 

summer mode:

 turning the mode selector to the summer symbol “

” (fig. 

2a) the traditional function of only domestic hot water is activated. If there is 

a domestic hot water request, the boiler switches on and the boiler status 

indicator LED (1) lights up with a fixed green light. The digital monitor (5) 

indicates the domestic hot water temperature (fig. 4a). 

 

winter mode:

 turning the mode selector to the area divided in segments (fig. 

2b) the boiler provides hot water and heating. If there is a heat request, the 

boiler switches on and the boiler status indicator LED (1) lights up with a fixed 

green light. The digital monitor (5) indicates the heating water temperature 

(fig. 3a). If there is a domestic hot water request, the boiler switches on and 

the boiler status indicator LED (1) lights up with a fixed green light. The digital 

monitor (5) indicates the domestic hot water temperature (fig. 4a).

Adjust ambient thermostat to desired temperature (approximately 20°C) 

Adjustment of the heating water temperature 

To  adjust  the  heating  water  temperature,  turn  the  knob  with  symbol  “

” 

 

(fig. 5a) to the area divided in segments 

Adjustment of domestic hot water temperature

To adjust domestic water temperature (bathrooms, showers, kitchen, etc.), turn 

the knob with symbol “

” (fig. 6a): to one of the numerical values within 1 (min 

value  37 °C) and 9 (max. value 60 °C). 

Pre-heating

 (faster hot water): rotate the domestic hot water temperature ad

-

justment knob (3 - fig. 1a) to the “

” symbol, then rotate it in line with one of 

the numbers between 1 (min. value 37°C) and 6 (max. value 60°C) (fig. 6a) to 

activate the pre-heating function. This function keeps the water in the domestic 

hot water exchanger hot, to reduce standby times when a request is made. 

When the pre-heating function is enabled, the yellow LED (1) in line with the “

” symbol is ON. The monitor (5) indicates the delivery temperature of the 

heating water or the domestic hot water, according to the current request. Dur

-

ing burner ignition following a pre-heating request, the monitor indicates the 

 

symbol. To deactivate the pre-heating function, rotate the domestic hot water 

temperature adjustment knob to the 

 symbol. The yellow LED will switch off. 

Bring the domestic hot water temperature adjustment knob back to the required 

position. This function cannot be activated when the boiler is OFF: function se-

lector (2   fig.1a) on “ ” OFF. If the red indicator light near the “

” symbol on 

the command panel lights up, this means the boiler is in temporary stop status 

(see the chapter about light signals and faults). The digital monitor indicates the 

fault code detected (fig. 8a).

Environment Automatic Adjustment System Function (S.A.R.A.) fig. 10a

By  setting  the  heating  water  temperature  selector  to  the  area  marked  by 

AUTO, the S.A.R.A. self-adjusting system is activated (frequency 0.1 sec. on; 

0.1 sec. off; duration 0.5): according to the temperature set on the ambient 

thermostat and the time employed to reach it, the boiler varies automatically 

the heating water temperature reducing the operating time, allowing great 

operation comfort and energy saving.

On the control panel, the green LED flashes with a frequency of 0.5 second 

ON, 3, 5 seconds OFF.

Reset function

To restore operation, set the function selector to “ ” (fig. 11a), wait 5-6 sec

-

onds then bring the function selector to the required position, checking that 

the red indicator light is OFF.

At this point the boiler will automatically start and the red lamp switches on 

in green.

N.B.

 If the attempt to reset the appliance does not activate operation, contact 

the Technical Assistance Service.

3A SWITCHING OFF

Temporary switching off

In case of absence for short periods of time, set the mode selector to “

OFF (fig. 11a). Anti-frost device remains active. The monitor appears as in 

fig. 4.2.a.

Long period switching off

In case of absence for long periods of time, set the mode selector to “

OFF (fig. 11a).

Then, close the gas tap present on the system . In this case, anti-frost device 

is deactivated: empty the systems, in case of risk of frost.

4A CONTROLS

Make sure at beginning of heating period and during use that the water pres

-

sure gauge indicates the pressure values with cold appliance within 0.6 and 

1.5 bar: this avoids system noise levels due to the presence of air.

In case of insufficient water circulation, the boiler will switch off. Under no cir

-

cumstances, water pressure must be below 0.5 bar (red field).

If this condition is checked, it is necessary to restore water pressure in the 

boiler proceeding as follows:

-  set the mode selector (2 - fig.1a) to ”  ”  OFF

-  turn on the filling tap (fig. 13a) until the pressure value is between 1 and 

 

1.5 bar.

Carefully close the tap.

Replace the mode selector on the initial position.

If pressure drop is frequent, contact the Technical Assistance Service. 

5A LIGHT SIGNALS AND FAULTS

The control panel has two led that indicate the boiler operating status:

Green led

Flashing

-  Flashing with frequency 0.5 second on - 3.5 seconds off = boiler in standby, 

there is no flame.

-  Flashing with frequency 0.5 second on - 0.5 second off = temporary stop of 

the appliance due to the following self-restoring faults:

-  water pressure switch (standby time 10 minutes approximately)

-  transitory waiting for ignition.

In this phase, the boiler waits for restoration of working conditions. If after standby 

time, the boiler will not restore regular operation, stop will be permanent and 

light signalling will be red.

-  Fast flashing (frequency 0.1 sec. on; 0.1 sec. off; duration 0.5)  input/output 

function S.A.R.A. (Italian acronym for Environment Automatic Adjustment 

System) - Fig. 10a.

  By setting the heating water temperature selector to the area marked by AUTO 

- temperature value from 55 to 65°C -  the S.A.R.A. self-adjusting system is 

activated: the boiler varies the delivery temperature according to the closing 

signal of the ambient thermostat. When the temperature set with the heating 

water temperature selector is reached, a 20 minutes count begins. If during 

this period the ambient thermostat still requests heat, the value of the set 

temperature automatically increases by 5 °C. 

  When the new value is reached, other 20 minutes count begins.

  If during this period the ambient thermostat still requests heat, the value of 

the set temperature automatically increases by 5 °C.

  This new temperature value is the result of the temperature set manually 

with the heating water temperature selector and the increase of +10 °C of the 

S.A.R.A function

  After the second increasing cycle, the temperature value is restored to the 

value set by the user and the above mentioned cycle is repeated until the 

ambient thermostat request is fulfilled.

Fixed green

 

If there is a flame, the boiler works regularly.

Red led

If the red LED lights up, this indicates the presence of a fault; the monitor visu

-

alises a code interpreted as follows:

A 01

 flame failure (fixed red LED + flame failure icon “

”)

A 02

 limit thermostat intervention (blinking red LED)

A 03

 limit thermostat intervention (fixed red LED)

A 04

 water pressure switch after the transitory phase (fixed red LED + filling 

icon “

”)

A 06

 domestic hot water NTC probe (blinking green + red LEDs)

A 07

 heating NTC probe (fixed red LED)

To restore operation: faults A 01-02-03

Position the function selector on “ ” OFF, wait 5-6 seconds then rotate it to the 

required position (summer) “ 

” or “

” (winter). If the reset attempts do not 

reactivate the boiler, contact the Technical Assistance Centre.

Fault A 04

Along with the fault code, the digital monitor visualises the   symbol. Check the pres

-

sure value indicated by the hydrometer: if it is less than 0.3 bar, position the function 

selector on 

 (OFF) and adjust the filling tap until the pressure reaches a value be

-

tween 1 and 1.5 bar. Position the function selector on the required position (summer) 

 

 or 

 (winter). If these pressure drops occur frequently, contact the Techni

-

cal Assistance Centre.

Fault A 06

The boiler functions normally but does not guarantee a constant domestic hot 

water temperature, which remains set at around 50°C.

Fault A 07

Contact the Technical Assistance Centre.

Fixed yellow LED

Pre-heating function activated.

Summary of Contents for Mynute J 24 C.A.I. E

Page 1: ...MANUAL DE INSTALARE I UTILIZARE DE INSTALLATIONS UND BEDIENUNGSANLEITUNG SL PRIRO NIK ZA MONTA O IN UPORABO HR PRIRU NIK ZA INSTALATERE I KORISNIKE SRB PRIRU NIK ZA MONTA U I KORI ENJE SK N VOD NA IN...

Page 2: ...le aparatului 84 Circuitul hidraulic 85 Schemele electrice 90 Prevalen a rezidual a circulatorului 93 Mynute J 24 28 C A I E entspricht den grundlegenden Anforderungen der folgenden Richtlinien Gas Ri...

Page 3: ...mmable containers and substances in the installation room Keep packaging materials out of reach of children Do not cover or reduce the size of the ventilation openings in the room where the boiler is...

Page 4: ...with cold system following this instructions turn by two or three turns the automatic relief valve cap A make sure the cold water inlet tap is open open the filling tap B until the pressure indicated...

Page 5: ...or on OFF and adjust the filling tap until the pressure reaches a value be tween1and1 5bar Positionthefunctionselectorontherequiredposition summer or winter If these pressure drops occur frequently co...

Page 6: ...t clean panels painted parts and plastic parts with paint thinner Panel cleaning must be carried out only with soapy water 5 1 Check the combustion parameters To carry out the combustion analysis proc...

Page 7: ...s on in green N B If the attempt to reset the appliance does not activate operation contact the Technical Assistance Service 3a SWITCHING OFF Temporary switching off In case of absence for short perio...

Page 8: ...Heating reduced thermal power kW 8 89 9 14 kcal h 7 647 7 859 Domestic hot water reduced thermal output Hi kW 10 40 10 70 kcal h 8 944 9 202 Domestic hot water reduced thermal power kW 8 89 9 14 kcal...

Page 9: ...ositifs de s curit ou de r glage sans l autorisation ou les indications du constructeur ne pas tirer d tacher retordre les c bles lectriques sortant de la chaudi re m me si celle ci est d branch e du...

Page 10: ...alis s il est possible de remplir l ins tallation de chauffage Cette op ration doit tre r alis e avec l installation froide en effectuant les op ra tions suivantes ouvrir le bouchon du purgeur d air a...

Page 11: ...sur teint OFF et agir sur le robinet de remplissage jusqu ce que la pression atteigne une valeur comprise entre 1 et 1 5 bar Mettre ensuite le s lecteur de fonction dans la position souhait e t ou hi...

Page 12: ...uniquement avec de l eau savonneuse 5 1 V rification des param tres de combustion Pour analyser la combustion effectuer les op rations suivantes ouvrir un robinet d eau chaude au d bit maximum placer...

Page 13: ...nctionnement s adresser au Service apr s vente 3a EXTINCTION Extinction provisoire En cas de courtes absences placer le s lecteur de fonction sur OFF Fig 11a La fonction antigel reste active L affiche...

Page 14: ...Puissance thermique minimale chauffage kW 8 89 9 14 kcal h 7 647 7 859 D bit thermique minimal sanitaire Hi kW 10 40 10 70 kcal h 8 944 9 202 Puissance thermique minimale sanitaire kW 8 89 9 14 kcal...

Page 15: ...s el ctricos que sobresalgan de la caldera aunque est desconectada de la red de alimentaci n el ctrica Evitar tapar o reducir dimensionalmente las aperturas de aireaci n del local de instalaci n No de...

Page 16: ...ca de purgado de aire A asegurarse de que el grifo de entrada de agua fr a est abierto abrir el grifo de llenado B hasta que la presi n indicada por el hidr metro est comprendido 1 y 1 5 bar Cuando se...

Page 17: ...5 bar Colocar a continuaci n el selector de funci n en la posici n deseada verano o invierno Si los descensos de presi n son frecuentes solicitar la intervenci n del Servicio T cnico de Asistencia An...

Page 18: ...pe ratura del agua sanitaria al valor m ximo fig 22 introducir la toma de an lisis de humos en el tramo de tubo rectil neo colocado despu s de la salida de la campana El agujero para la inserci n de l...

Page 19: ...OFF fig 11a Luego cerrar el grifo del gas presente en la instalaci n En este caso la funci n antihielo quedar desactivada Vaciar las instalaciones si hubiese riesgo de hielo 4a CONTROLES Aseguarse al...

Page 20: ...8 944 9 202 Potencia m nima til calefacci n kW 8 89 9 14 kcal h 7 647 7 859 Potencia m nima nominal sanitario Hi kW 10 40 10 70 kcal h 8 944 9 202 Potencia m nima til sanitario kW 8 89 9 14 kcal h 7...

Page 21: ...al do painel de comando em OFF proibido modificar os dispositivos de seguran a ou de regula o sem a autoriza o ou as indica es do fabricante N o puxar retirar torcer os cabos el ctricos que saem da ca...

Page 22: ...uecimento fig 14 Efectuadas as conex es hidr ulicas pode se proceder ao enchimento da insta la o de aquecimento Esta opera o deve ser executada com a instala o fria efectuando as seguintes opera es ab...

Page 23: ...to at a press o atingir um valor compreendido entre 1 e 1 5 bar Posicionar posteriormente o selector de fun o na posi o desejada ver o ou inverno Se as quedas de press o s o frequentes solicitar a int...

Page 24: ...1 Verifica o dos par metros de combust o Para efectuar a an lise da combust o executar as seguintes opera es abrir uma torneira da gua quente na vaz o m xima coloque o selector de fun o em ver o fig 2...

Page 25: ...desbloqueio n o activarem o funcionamento chamar o Centro de Assist ncia T cnica 3a DESLIGAMENTO Desligamento tempor rio Em caso de breves aus ncias posicionar o selector de fun o em OFF fig 11a A fu...

Page 26: ...40 10 70 kcal h 8 944 9 202 Pot ncia t rmica reduzida aquecimento kW 8 89 9 14 kcal h 7 647 7 859 Pot ncia t rmica reduzida sanit rio Hi kW 10 40 10 70 kcal h 8 944 9 202 Pot ncia t rmica reduzida san...

Page 27: ...l sba ll tja A gy rt felhatalmaz sa vagy tmutat sai n lk l tilos m dos t sokat v gezni a biztons gi vagy szab lyoz szerkezeteken Ne h zza szak tsa vagy tekerje a kaz n elektromos k beleit m g akkor se...

Page 28: ...szeinek cser je sor n kiz r lag eredeti alkatr szeket haszn ljon 3 6 F t si rendszer felt lt se 14 bra Miut n a hidraulikus bek t ssel v gzett hozz l that a f t si rendszer felt lt s nek A k vetkez m...

Page 29: ...04 Adigit liskijelz nahibak donk v la Ellen rizzeav znyom sm r ltalmu tatottnyom s rt ket haaz rt kkevesebb mint0 3bar ll tsaafunkci v laszt gombotkikapcsolt OFF ll sba majdnyissakiafelt lt csapot am...

Page 30: ...l kony anya gokat p ld ul benzin alkohol stb A k ls bor t lemezeket a f nyezett s a m anyag r szeket ne tiszt tsa fest khez haszn latos old szerrel A k ls bor t lemezeket csak szappanos v zzel szabad...

Page 31: ...dre v lt t Megjegyz s Ha a felold si k s rletek nem ind tj k el a m k d st k rje a Vev szolg lati szerviz seg ts g t 3a KIKAPCSOL S Kikapcsol s r videbb id szakra R videbb t voll t eset n ll tsa a fun...

Page 32: ...jes tm ny f t s kW 8 89 9 14 kcal h 7 647 7 859 R szleges h terhel s HMV Hi kW 10 40 10 70 kcal h 8 944 9 202 R szleges h teljes tm ny HMV kW 8 89 9 14 kcal h 7 647 7 859 Hat sfok max h teljes tm ny m...

Page 33: ...iciun fel fantele de aerisire din nc perea unde se instaleaz cazanul NU l sa i recipiente cu substan e inflamabile n nc perea unde se instaleaz cazanul NU l sa i ambalajele la ndem na copiilor Evita i...

Page 34: ...ala ia proceda i astfel opri i cazanul deschide i robinetul de golire a cazanului C goli i instala ia elimin nd apa din punctele cele mai joase ale acesteia 3 8 Golirea instala iei de ap menajer De fi...

Page 35: ...icita i interven ia Serviciului Tehnic de Asisten Led galben cu iluminare permanent Func ie pre nc lzire activ C nd cele dou leduri se aprind alternat nseamn c este n curs de des f urare o procedur de...

Page 36: ...arse trebuie introdus p n ce ajunge la opritor alimenta i electric cazanul Aparatul func ioneaz la puterea maxim i deci se poate efectua controlul arderii La finalul analizei nchide i robinetul de ap...

Page 37: ...pozi iona i selectorul de func ii pe OFF fig 11a nchide i robinetul de gaze al instala iei n acest caz func ia de protec ie la nghe se dezactiveaz goli i instala ia dac exist riscul de nghe 4a CONTROA...

Page 38: ...redus nc lzire kW 8 89 9 14 kcal h 7 647 7 859 Putere termic redus circ menajer Hi kW 10 40 10 70 kcal h 8 944 9 202 Putere termic redus circ menajer kW 8 89 9 14 kcal h 7 647 7 859 Randament util Pn...

Page 39: ...l sen und verdrehen Sie nicht die aus dem Kessel austretenden Kabel auch wenn dieser vom Stromversorgungsnetz getrennt ist Vermeiden Sie es die Bel ftungs ffnungen des Installationsraumes zu verschli...

Page 40: ...Original Ersatzteile verwendet werden 3 6 F llen der Heizanlage Abb 14 Nach Herstellung der Wasseranschl sse kann die Heizanlage gef llt werden Dieser Vorgang muss bei kalter Anlage wie folgt ausgef...

Page 41: ...e gew nschte Position Sommer oder Winter Sollte es h ufig zu einem Druckabfall kommen muss der Technischer Kundendienst angefordert werden St rung A 06 Der Kessel funktioniert normal gew hrleistet abe...

Page 42: ...nnungsparameter F hren Sie zur Analyse der Verbrennung folgende Arbeitsg nge aus ffnen Sie ein Ventil des Warmwassers bis zum maximalen Durchsatz Stellen Sie den Funktionswahlschalter auf Sommer Abb 2...

Page 43: ...ur Entst rung nicht den Betrieb aktivieren den Technischen Kundendienst 3A AUSSCHALTEN Vor bergehendes Ausschalten Stellen Sie bei l ngerer Abwesenheit den Funktionswahlschalter auf OFF Abb 11a Die Fr...

Page 44: ...z Hi kW 10 40 10 70 kcal h 8 944 9 202 Reduzierte W rmeleistung kW 8 89 9 14 kcal h 7 647 7 859 Reduzierter W rmedurchsatz Sanit r Hi kW 10 40 10 70 kcal h 8 944 9 202 Reduzierter W rmeleistung Sanit...

Page 45: ...ala e ne pu ajte na dosegu otrok Odprtin za zra enje prostora monta e ne zapirajte in ne zmanj ujte njihove velikosti Prezra evalne odprtine so za pravilno zgorevanje nujno potrebne 2 OPISKOTLA Mynute...

Page 46: ...i ventil kotla C izpraznite na najni jih mestih napeljave 3 8 Praznjenje sistema sanitarne vode Vsakokrat ko preti nevarnost zmrzovanja se mora sistem sanitarne voda izprazniti s posegom na naslednji...

Page 47: ...acije maksimalne mo i se mora izvesti v navedenem vrstnem redu in jih lahko opravi izklju no usposobljeno osebje odstranite okrov tako da odvijete pritrdilne vijake A slika 15 za pribli no dva vrtljaj...

Page 48: ...ranje dimnih plinov se mora vstaviti do konca vklopite elektri no napajanje kotla Naprava deluje z maksimalno mo jo in lahko se izvede kontrolo zgorevanja Po opravljeni analizi zaprite pipo tople sani...

Page 49: ...postavite na OFF slika 11a Zaprite plinsko pipo ki se nahaja na napeljavi V tem primeru je funkcija za ite pred zamrznitvijo izklopljena e je prisotna nevarnost zamrznitve sistem izpraznite 4a KONTROL...

Page 50: ...kcal h 8 944 9 202 Zmanj ana toplotna mo ogrevanja kW 8 89 9 14 kcal h 7 647 7 859 Zmanj ana toplotna mo sanitarne vode Hi kW 10 40 10 70 kcal h 8 944 9 202 Zmanj ana toplotna mo sanitarne vode kW 8 8...

Page 51: ...rije u kojoj je postavljen kotao Zabranjeno je ostavljati kartonske kutije i zapaljive tvari u prostoriji u kojoj je postavljen ure aj Zabranjeno je ostavljati ambala u djeci na dohvat ruke Treba izbj...

Page 52: ...a pa nije potreban nikakav ru ni zahvat Plamenik se pali tek po zavr etku faze ispu tanja zraka 3 7 Pra njenje instalacije grijanja Za pra njenje instalacije postupite na slijede i na in ugasite kotao...

Page 53: ...A 06 Kotao radi normalno ali ne jam i se stabilnost temperature sanitarne vode koja ostaje namje tena na temperaturu oko 50 C Pogre ka A 07 Zatra ite zahvat Servisa za tehni ku pomo Stalno upaljena u...

Page 54: ...a izlaza kape u skladu s va e im propisima slika 23 Osjetnik za analizu dimnih plinova mora se gurnuti sve dok se ne uglavi Uklju ite elektri no napajanje kotla Ure aj radi s maksimalnom snagom i mo e...

Page 55: ...olo aj OFF fig 11a Zatim zatvorite plinski ventil na instalaciji U tom slu aju funkcija protiv smrzavanja je isklju ena ispustite vodu iz instalacija ako postoji opasnost od smrzavanja 4a PROVJERE Pro...

Page 56: ...grijanja Hi kW 10 40 10 70 kcal h 8 944 9 202 Smanjena toplinska snaga grijanja kW 8 89 9 14 kcal h 7 647 7 859 Smanjeno toplinsko optere enje sanitarne funkcije Hi kW 10 40 10 70 kcal h 8 944 9 202...

Page 57: ...u deci na dohvat ruke Treba izbegavati zapu avanje ili smanjivanje veli ine ventilacionih otvora od lokalnih instalacija Otvori za ventilaciju su neophodni za pravilno sagorevanje 2 opis KOTLA Mynute...

Page 58: ...e otvorite sve slavine tople i hladne vode ispustite vodu na najni im ta kama instalacije Napomena Ispust sigurnosnog ventila D aparata treba da se pove e na odgovaraju i sistem sakupljanja i odvo en...

Page 59: ...orekcija 4 5 Pode avanja Kotao je ve u fazi izrade uskla en odre enim pravilima i funkcijama Me utim ako bi bilo neophodno napraviti dodatna uskla ivanja kao to se de ava kada je u pitanju zamena vent...

Page 60: ...ezbednost Priru nik za ru nu upotrebu je sastavni deo proizvoda i zbog toga mora pa ljivo da se koristi i da se prate uputstva pri svakom kontaktu sa proizvodom u slu aju gubitka ili o te enja uputstv...

Page 61: ...hladna vrednosti pritiska izme u 0 6 i 1 5 bar zato je neophodno izbegavati bilo kakvo izlaganje o te enju proizvoda gde je potrebno prisustvo vazduha U slu aju da je nedovoljna cirkulacija vode kota...

Page 62: ...enog zagrevanja Hi kW 10 40 10 70 kcal h 8 944 9 202 Termi ko zagrevanje dovodi do umanjenog zagrevanja kW 8 89 9 14 kcal h 7 647 7 859 Termi ko zagrevanje dovodi do umanjenog sanitarnog zagrevanja Hi...

Page 63: ...eniu prierezov vetrac ch otvorov v miestnosti v ktorej je kotol nain talovan Nenech vajte n doby v ktor ch boli s ulo en z paln l tky ani samot n z paln l tky v miestnosti v ktorej je nain talovan zar...

Page 64: ...naplni rozvod vykurovania Pri plnen mus by rozvod vychladnut a v r mci tohto je potrebn otvori o dve alebo tri ot ky uz ver automatick ho odvzdu ovacieho ventilu A uisti sa e je otvoren ventil pr vod...

Page 65: ...ho vr te sp do po adovanej polohy leto alebo zima Ak sa po t chto konoch kotol neodblokuje po iadajte o z sah Servisn slu bu Porucha A 04 Na digit lnom displeji bude okrem k du poruchy zobrazen aj sym...

Page 66: ...rametrov spa ovania Pre anal zu spa ovania s potrebn nasledovn kony otvorte ventil teplej vody aby bol dosiahnut maxim lny prietok nastavte voli re imu innosti do polohy leto obr 22 a voli teploty T V...

Page 67: ...dobie Pri dlh om vyraden kotla z innosti prepnite voli re imu innosti na VYP obr 11a Potomzatvorteventilpr voduplynu umiestnen narozvode Vtomtopr pade d jde k vypnutiu funkcie ochrany proti zamrznutiu...

Page 68: ...40 10 70 kcal h 8 944 9 202 Zn en tepeln v kon vykurovania kW 8 89 9 14 kcal h 7 647 7 859 Zn en tepeln prietok okruhu T V Hi kW 10 40 10 70 kcal h 8 944 9 202 Zn en tepeln v kon okruhu T V kW 8 89 9...

Page 69: ...vimo element vaikams pasiekiamoje vietoje neu denkite ir nesuma inkite patalpos ventiliacijos ang Ventiliacijos angos yra b tinos kad b t geras degimas 2 ILDYMO KATILO apra ymas Mynute J 24 28 C A I E...

Page 70: ...n vandentiekio iaup atsukite kar to ir alto vandens iaupus i leiskite vanden i emiausi renginio viet D MESIO Apsauginis i leidimo vo tuvas D turi b ti prijungtas prie tinkamos nuotek surinkimo sistemo...

Page 71: ...entr Geltonas viesos diodas Pa ildymo funkcija aktyvuota Jei viesos diodai mirksi pakaitomis tai rei kia kad atliekamas kalibravimas 4 5 Reguliavimas ildymo katilas jau sureguliuotas gamintojo Ta iau...

Page 72: ...j kreipkit s technin s prie i ros centr d l naujo egzemplioriaus ildymo katilo montavimas ir bet kokie technin s pagalbos ir prie i ros darbai turi b ti atliekami kvalifikuot darbuotoj laikantis vieto...

Page 73: ...b du neturi b ti emesnis nei 0 5 baro raudonas laukas Jei taip atsitikt reikia atstatyti ildymo katilo vandens sl g iuo b du nustatyti veiksenos selektori 2 1a pav ties OFF atsukti pripildymo iaup 13a...

Page 74: ...ildymo ilumos galia kW 8 89 9 14 kcal h 7 647 7 859 Suma intas kar to vandens ilumos srautas Hi kW 10 40 10 70 kcal h 8 944 9 202 Suma inta kar to vandens ilumos galia kW 8 89 9 14 kcal h 7 647 7 859...

Page 75: ...MYNUTE J C A I E 75 GR 1 1 2 bar 3 bar OFF 2 Mynute J 24 28 C A I E B11BS 3 50 3...

Page 76: ...A 9 89 24 Vdc 3 5 mm EN 60335 1 III 230 Volt 50 Hz 85 W EN 60335 1 L N HAR H05V2V2 F 3 x 0 75 mm 2 7 mm 3 4 3 5 2 13 11 12 10 3 6 14 A B 1 1 5 bar 3 7 C 3 8 D 4 4 1 Beretta 4 2 2 1 2 led 1 5 4a 2 led...

Page 77: ...55 65 C S A R A 20 5 C 20 5 C 10 C S A R A Led led A 01 led A 02 led A 03 led A04 led A 06 NTC led A 07 NTC led A 01 02 03 OFF 5 6 A 04 0 3 bar OFF 1 1 5 bar A 06 50 C A 07 Led led 4 5 A 15 4 5 1 16...

Page 78: ...78 JP2 OFF 4 6 G20 LPG 21 19 LPG JP3 LPG JP3 5 5 1 22 22 23 1 1 bar...

Page 79: ...10 AUTO S A R A 0 1 0 1 0 5 led 0 5 3 5 11 5 6 3 OFF 11 4 2 a OFF 11 4 0 6 1 5 bar 0 5 bar 2 1 OFF 13 1 1 5 bar 5A led Led 0 5 3 5 0 5 0 5 10 0 1 0 1 0 5 S A R A 10 AUTO 55 65 C S A R A 20 5 C 20 5 C...

Page 80: ...O 20 203 9 28 30 285 5 305 9 37 377 3 mbar mm H2O 13 5 137 7 24 C A I Hi kW 26 70 31 90 kcal h 22 962 27 434 kW 24 11 28 97 kcal h 20 735 24 910 Hi kW 10 40 10 70 kcal h 8 944 9 202 kW 8 89 9 14 kcal...

Page 81: ...at adjustment indicates the connection to an external probe Flame failure this icon is visualised together with irregularity code A 01 Irregularity indicates any operating irregularities together with...

Page 82: ...faptul c este n desf urare un ciclu de pre nc lzire arz torul este aprins Temperatur nc lzire ap cald menajer sau anomalie n func ionare SL F Krmilna plo a 1 Led za signaliziranje stanja kotla 2 Izbi...

Page 83: ...o kvar koji je kodiran ifrom kvaraA04 Termoregulacija pokazuje spajanje preko spoljne sonde Plamen je blokiran i tada e ova ikona da bude ozna ena kao kvar koji je kodiran ifrom kvaraA01 Kvar predstav...

Page 84: ...rio 12 Term stato de fumos 13 Permutador bit rmico 14 Vaso de expans o 15 Transformador de acendimento remoto 16 Sonda NTC sanit rio 17 Intercambiador sanit rio 18 V lvula do g s 19 Flux metro HU Kaz...

Page 85: ...Circulador com respiro 11 V lvula de desgasifica o 12 Vaso de expans o 13 Sonda NTC prim rio 14 Permutador bit rmico 15 Pressostato da gua 16 Queimador 17 Intercambiador sanitario 18 Sonda NTC sanit r...

Page 86: ...jiva sanitarne vode 18 Sanitarna NTC sonda 19 Slavina za punjenje 20 Grani nik protoka 21 Flusostat 22 Filter HR HIDRAULI KI SUSTAV 1 Ulaz sanitarne vode 2 Izlaz sanitarne vode 3 Dovod grijanja 4 Povr...

Page 87: ...w Haszn lati melegv z maxim lis nyom sa Pms F t s maxim lis nyom sa T H m rs klet Hat sfok D Specifikus terhel s NOx NOx oszt ly RO ETICHET MATRICOL Func ie ap menajer Func ie nc lzire Qn Capacitate t...

Page 88: ...eln prietok Pn Tepeln v kon IP Trieda ochrany Pmw Maxim lny prev dzkov tlak okruhu T V Pms Maxim lny tlak okruhu vykurovania T Teplota innos D pecifick prietok NOx Trieda NOx GR Qn Pn IP Pmw Pms T D N...

Page 89: ...ne mic vor fi cupla i a a cum se arat n fig conectorului CN6 C R telecomand SE sond extern DE Anschluss des Raumthermostats T A Raumthermostat A Das Raumthermostat 24V wird wie im Schema angegeben ein...

Page 90: ...ot water flow meter F L N Il est conseill d utiliser la polarisation L N Bleu Blue Marron Brown Noir Black Rouge Red Blanc White Violet Violet Gris Grey A Jumper du thermostat dans un environnement de...

Page 91: ...P Szivatty S S Haszn lati melegv z h m rs klet rz kel je NTC PA F t s presszoszt tja MOD Modul tor szab lyoz 3V Szervomotor h rom g szelepe FS Haszn lati meleg v z raml sm r je RO L N Se recomand pola...

Page 92: ...N Blue Brown Black Red White Violet Grey A B 24V C A R D 3 15A F MP P1 reset P2 P3 P4 JP1 JP2 JP3 MTN LPG JP4 JP5 JP6 LED Led 1 Led 2 Led 3 CN1 CN12 CN4 F1 2A T F 3 15A F M3 T A E A R TRX T F S R NTC...

Page 93: ...t dac n schimb torul de c ldur circularea apei se face n mod corect eficient n acest scop cazanul este dotat cu un by pass automat care regleaz debitul de ap n schimb torul de c ldur n orice situa ie...

Page 94: ...A Szobatermoszt t RO F Rezisten A Alimentare T A Termostat clim DE F Sicherung A Stromversorgung T A Raumthermostat SL F Osigura A Izvor napajanja T A Sobni termostat HR F Osigura A Napajanje T A Pros...

Page 95: ...C DIE FASTONANSCHL SSE D DIE REGELMUTTER EINES LEISTUNGSMAXIMUM E INBUSSCHRAUBE EINES MINIMUM DIE GESUNDHEITSFUNKTION SL A MERILNI PRIKLJU EK PRED VENTILOM PLINA B ZA ITNI POKROV EK C SPONKI FASTON D...

Page 96: ...s be ll t sa MAX maximum f t s be ll t sa DE JP1 berbr ckung zur Aktivierung der Einstellfunktion JP2 berbr ckung zur Einstellung des Maximums Heizung JP3 berbr ckung zur Auswahl von MTN Fl ssiggas SL...

Page 97: ...MYNUTE J C A I E 97 fig 7a fig 2b fig 3a fig 5a fig 6a fig 2a fig 4a 4 1 2 3 5 fig 1a...

Page 98: ...dicador luminoso verde LR indicador luminoso rojo PT LV led verde LR led vermelho HU LV z ld led LR piros led RO LV led verde LR led ro u DE LV gr ne Led LR rote Led SL LV zelena led LR rde a led HR L...

Page 99: ...MYNUTE J C A I E 99...

Page 100: ...Cod 20015273 09 09 Ed 0...

Reviews: