GENERAL
6 TECHNICAL SPECIFICATIONS
DESCRIPTION
IDRA MS
200
300
430
550
Type of storage cylinder
Vitrified
Storage cylinder layout
Vertical
Heat exchanger layout
Vertical
Storage cylinder capacity
208
305
442
556
l
Diameter of storage cylinder with insulation
605
755
mm
Height with insulation
1330
1840
1630
1980
mm
Insulation thickness
50
mm
Diameter/length of magnesium anode
33/450
33/520
mm
Flange diameter
118
mm
Diameter/length of sensor sockets
16/175
mm
Sleeve for electric heating element (not supplied)
1 1/2” F
Ø
Coil water capacity
5,7
9,3
11
12,8
l
Coil heat exchange surface area
0,94
1,53
1,8
2,1
m2
Maximum operating pressure of storage cylinder
10
bar
Maximum operating pressure of coil
10
bar
Maximum operating temperature
99
°C
Net weight with insulation
70
100
135
150
kg
Heat loss according to EN 12897:2006 at ∆T=45 °C
116
93
91
114
W
Energy efficiency class
E
C
Pressure drops COIL
PRESSURE DROP (mbar)
0
0
200
50
100
150
200
250
300
400
600
800
1000
1200
1400
1600
550
430
300
200
FLOW RATE (l/h)
Tests performed with a 30% glycol/water solution.
Summary of Contents for IDRA MS 200