Par
.
no.
Parameter
Number of
elements
T
ype
Edit
V
alue range
Min Max
Resolution
Default
setting
Password
level
645
Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
1
Std_u8
edit
0
2
1
0
SO
652
VSD behavior when safety loop / burner flange is open
0 =
no VSD control when safety loop / burner flange is
open
1 =
VSD control independent of safety loop / burner
flange
1
Std_u8
edit
0
1
1
1
HF
653
VSD standstill supervision in standby mode
0 = deactivate
1 = active
1
Std_u8
edit
0
1
1
1
HF
700
Error history
701
Error history: 701-725.01.Code
25
Std_u8
read only
0
255
1
0
Info / Service
•
Error history: 701-725.02.Diagnostic code
25
Std_u8
read only
0
255
1
0
Info / Service
•
Error history: 701-725.03.Error class
25
Std_u8
read only
0
6
1
0
Info / Service
•
Error history: 701-725.04.Phase
25
Std_u8
read only
0
255
1
0
Info / Service
•
Error history: 701-725.05.Startup counter
25
Std_s32
read only
0
99999999
1
0
Info / Service
725
Error history: 701-725.06.Output
25
Output
read only
0%
100 %
0.1%
0%
Info / Service
900
Process data
903
Current output
Index 0 = fuel
Index 1 = air
2
Output
read only
0%
100%
0.1%
0%
Info / Service
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
2
Std_s16
read only
-50°
150°
0.01°
0°
Info / Service
935
Absolute speed
1
Std_u16
read only
0
6553.5
0.1
0
SO
936
Standardized speed
1
Std_s16
read only
-200%
200%
0.1%
0%
Info / Service
942
Active load source
1 = output during curve settings
2 = manual output
3 = default output via building automation
4 = default output via analog input
5 = external load controller via contacts
1
Selection
read only
0
255
1
0
SO
Summary of Contents for B 45i A2.2H J/K